CIO-110 Setup
Purpose/Scope
5 min.
Procedure
WBPEEUI240751C0
This procedure gives the steps required to set up the CIO-110
block for proper operation.
None.
Parts
Small-tipped, flat-blade screwdriver.
Tools
Needlenose pliers (optional).
IISAC01 Analog Control Station instruction.
1. Set the M/A power select jumpers J1 and J2 as appropri-
ate (Table PR15-1).
Table PR15-1. M/A Power Select Jumpers
Power Source
External M/A power source connected at
terminal block
LFP power used for M/A power; no external
M/A power source connected
Refer to Figure
IISAC01 Analog Control Station
IISAC01 Analog Control Station instruction for an explanation
IISAC01 Analog Control Station
IISAC01 Analog Control Station
of the M/A power.
2. Verify a 1.6 A, 250 V fuse is present in fuse holder XF3.
This fuse is required when using LFP power for M/A power.
3. Verify 4.0 A, 250 V fuses are present in fuse holders XF1
and XF2. These fuses are for the +24 VDC LFP power that
operates IISAC01 control stations connected at P2 and P4
respectively.
PR15-1
for jumper locations. Refer to the
PR15
J1
J2
1 2 3
1 2 3
4 5 6
4 5 6
1 2 3
1 2 3
4 5 6
4 5 6
PR15 - 1