I/O Channel (FC 222, 223, 224, 225)
WBPEEUI240751C0
The I/O channel function codes allow for single channel mod-
ularity. In other words, one I/O channel function code reads
the input value or drives the output of one channel. Specifica-
tions are set on a per channel basis rather than on an I/O
group basis. The function codes provide addressing, startup,
execute (i.e., run time), override, simulation, and failure mode
operation specifications. The I/O channel function codes are
exception reporting function codes.
Tables
6-1
and
6-2
summarize some of the I/O channel func-
tion code capabilities. Refer to the Function Code Applica-
tion Manual for detailed function code descriptions,
specifications, outputs, and capabilities.
Table 6-1. I/O Channel Function Code Summary
FC
I/O
222 Analog input
Reads analog input
channel data.
223 Analog output Sets analog output
demand value and
acquires output channel
readback data.
224 Digital input
Reads digital input
channel data.
225 Digital output
Sets digital output state
and acquires output
channel readback data (if
applicable).
NOTE:
1. Not all digital output channels support readback. This depends on the I/O block type (e.g.,
DOT-100 block does not support readback).
Table 6-2. I/O Channel Specifications Summary
Specification Description
Alarming
Alarm state
High alarm (EU)
Low alarm (EU)
Purpose
Normal Mode Output
Analog input value in
engineering units and the
channel status.
Readback analog output
value in engineering units
and the channel status.
Digital input state (0 or 1)
and the channel status.
Readback digital output
state (0 or 1) and the
channel status.
1
Function Code
222
(AI)
Function Codes
223
224
225
(AO)
(DI)
(DO)
6 - 9