I/O Block Problem Reports

Table 8-3. Status Codes
(continued)
Code
LED On
26
0x1A – 2 – 4 5 – – – Duplicate device label
27
0x1B 1 2 – 4 5 – – – Incorrect Hnet
35
0x23 1 2 – – – 6 – – Write violation
49
0x31 1 – – – 5 6 – – Memory or CPU fault
50
0x32 – 2 – – 5 6 – – Bus error
51
0x33 1 2 – – 5 6 – – Illegal instruction
52
0x34 – – 3 – 5 6 – – Internal error - trace or
53
0x35 1 – 3 – 5 6 – – Internal error - spurious
54
0x36 – 2 3 – 5 6 – – Internal error - divide by
55
0x37 1 2 3 – 5 6 – – Internal error - unde-
56
0x38 – – – 4 5 6 – – Board level hardware
63
0x3F 1 2 3 4 5 6 – – Normal stop
64
0x40 – – – – – – 7 – Configuration
128
0x80 – – – – – – – 8 Normal operation
192 0xC0 – – – – – – 7 8 Normal operation
NOTE: – = off.
I/O Block Problem Reports
Problem reports are used to identify device and I/O channel
problems (Table 8-4). These reports can be seen on a human
system interface. The I/O device definition function code is
responsible for problem reporting. The Harmony controller
performs the actual reporting.
8 - 6
Condition
detected
connection
privilege error
or unassigned exception
0 or CHK instruction
fined TRAP instruction
error
downloaded
(backup I/O module)
(primary I/O module)
Corrective Action
Device label assigned to the block is
already in use by another I/O block.
Define a unique device label.
I/O block is connected to a peer-to-peer
network instead of Hnet.
Reset the I/O module. If error persists,
replace the I/O module.
Replace the I/O module.
Reset the I/O module.
Normal operation. No action required.
WBPEEUI240751C0