Selecting A Scale Range; Thermocouple Input Type; Platinum Rtd Type; Thermistor Input Type - Omron E5CS Manual

1/16 din sized controller offers selectable control, alarm modes
Hide thumbs Also See for E5CS:
Table of Contents

Advertisement

E5CS-X
J SELECTING A SCALE RANGE
Use the rotary DIP switch to select the temperature scale range.
The tables below show the switch setting number for each range.
The temperature indication range is the set temperature range
(full scale) ±10%, unless otherwise noted.
If the set temperature is shifted outside of changing the scale
range, the set temperature is displayed. It is then automatically

Thermocouple Input Type

Thermocouple input models are factory-set to switch position 2
for a temperature range of 0° to 400°, using a type K
thermocouple.
Switch setting
0
Temperature range
0 to 200 0 to 300 0 to 400 0 to 500 0 to 600 0 to 999 0 to 999 0 to 200 0 to 300 0 to 400 0 t0 500
°C
Scale indication
Unit of measure
1° C or F

Platinum RTD Type

Platinum RTD input models are factory-set to switch position 3
for a temperature range of 0.0° to 99.9°.
Switch setting
0
Temperature range
–50 to 50
°C
Scale indication
Unit of measure
1° C or F
Note: 1. Do not set the selector switch to position 9. This will cause error message "FFF" or "–––" to be displayed.
2. When changing scale ranges where the unit of measure changes 1° to 0.1° or vice versa, the set temperature also changes to
reflect the unit of measure. For example, with a set temperature of 100°, a change from a scale range with 1° resolution to 0.1°
makes the set temperature 10°; with a set temperature of 15°, a change in scale range resolution from 0.1° to 1° makes the set
temperature 150°.

Thermistor Input Type

Thermistor input models are factory-set to switch position 0 for a
temperature range of –50° to 50C°.
Switch setting
0
Temp. range
–50 to 50
°C
Scale indication
Unit of measure
1° C or F
Note: 1. The temperature indication range for a setting scale of –50° to 50°C is –50° to 60°C. It is the full scale ±10% with the other set-
ting scale ranges.
2. With a temperature range, such as 50° to 150°C, exceeds the factory-set range, the indication unit is automatically adjusted to
the minimum value. The set temperature is displayed upon power application.
1
2
3
°C
°C/°F
°C/°F
1
2
0.0 to 50.0
–20 to 80
°C
°C
0.1° C or F
1° C or F
1
2
3
0 to 100 50 to
100 to
150
200
changed to the maximum or minimum value of the newly set
temperature scale range.
If the alarm value is shifted outside the temperature scale range
as a result of changing the scale range, it is automatically
changed to the maximum value of the newly set scale range.
4
5
6
°C/°F
°C/°F
°F
3
4
5
0.0 to 99.9
0 to 200
0 to 300
°C/°F
°C/°F
°C
0.1° C or F
1° C or F
4
5
6
150 to
–50 to 100 0 to 200
300
°F
E5CS-X
6
7
8
°C
°C
°C/°F
6
7
8
0 to 400
0 to 600
0 to 800
°C/°F
°F
°F
7
8
9
100 to
200 to
300 to
300
400
600
9
°C/°F