Siemens P1-FLN Version
Installation and Operation Guide
NOTE: Also refer to Siemens' Application Note, Document No. 140-0280
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699
www.onicon.com • sales@onicon.com
07-18
0656-11 / 18320

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SYSTEM-10 and is the answer not in the manual?

Questions and answers

Summary of Contents for Onicon SYSTEM-10

  • Page 1 ONICON SYSTEM-10 BTU METER Siemens P1-FLN Version Installation and Operation Guide NOTE: Also refer to Siemens’ Application Note, Document No. 140-0280 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 www.onicon.com •...
  • Page 2 Messages identified as “Important Note” contain information critical to the proper operation of the product. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 3: Table Of Contents

    SYSTEM-10-P1 POINT DATABASE ............33 4.6.1 System-10-P1 Point Database ............33 COMMISSIONING ...................35 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 Page...
  • Page 4 BTU METER ANALOG OUTPUTS BOARD (with 4 analog outputs) A-25 CONDITIONS OF SALE 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 Page...
  • Page 5: Introduction

    B-directional dual mode BTU calculations are totalized, displayed and reported separately to the P1 network. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 6 (factory selectable) Note: Specifications are subject to change without notice. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 Page...
  • Page 7: Additional Required Hardware

    The serial numbers are unique identifiers that you should have available when contacting ONICON for assistance regarding your system. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 8: Unpacking

    BTU meter. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 9: Installation

    11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 10: Mechanical Installation

    DO NOT drill holes in the main unit. Use only the openings that are provided. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 11: Thermowell Installation

    11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 12 An internal o-ring seals the fluid. Contact ONICON for assistance in the event of a leak. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 13: Temperature Sensor Installation

    Additional cable may be added in the field if necessary, but must be of twisted shielded pair construction. (#22 gauge minimum and #18 gauge maximum) 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 14: Flow Meter Installation

    For F-1300 series inline turbine flow meters, refer to the documentation that is provided with the flow meter. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 15: Electrical Installation

    This product must be connected to earth ground for proper operation. Failure to do so may result in erratic operation. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 16 If this does not occur, disconnect power immediately and re-verify all wiring connections. If the problem persists, contact ONICON. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 17 This product must be connected to earth ground for proper operation. Failure to do so may result in erratic operation. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 18: Input Signal Connections

    Shield connections are required for proper operation. Failure to use shielded cable may result in erratic operation. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 19: Input Signal Connections From Insertion Turbine

    3.3.2.3 Input Signal Connections From F-2500 Flow Meters 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 20: Input Signal Connections From F-2600 & F-2700

    System-10 shield terminals and left unterminated at the flow meter. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 21: Input Signal Connections From F-3500 Meters

    See FB-3500 installation and operation guide for additional information on properly grounding the meter. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 22: Input Signal Connections From F-4200 Meters

    System-10 shield terminals and left unterminated at the flow meter. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 23: Contact Closure Output For Energy Total(S) And Mode

    MODE 2 1/4 AMP LED1 MODE STATUS Not Used 20075-50 REV. A 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 Page...
  • Page 24: Isolated Analog Output(S)

    Terminal T4 from flow meter. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 25: Network Signal Connections

    Incoming and outgoing RS485 cable shield wires should be connected together, but must not be connected to the System-10. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 26: Optional Isolated Digital Pulse Input (Di3)

    (S1) on the communications Circuit Board (Fig. 1) to the correct setting. Fig. 1 AUX PULSE INPUT (Di3) CONNECTOR (T2) 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 Page...
  • Page 27 Fig. 3 ONICON BTU Meter Di3 In (+) Di3 In (-) 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 Page...
  • Page 28 Fig. 5 ONICON BTU Meter Di3 In (+) Di3 In (-) 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 Page...
  • Page 29: System-10 Start-Up And Commissioning

    DEG F, DEG C RETURN TEMPERATURE DEG F, DEG C DIGITAL INPUT Di3 NONE 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 Page...
  • Page 30: Units And Multipliers

    ONICON for assistance. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 31: Entering A Network Address, Selecting The Flow Meter Location & Enabling / Disabling Front Panel Reset

    0-9. button. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 Page...
  • Page 32: Application Number

    TON-HRS x 10 GAL x 1,000 GPM x 1 DEG F 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 Page...
  • Page 33: System-10-P1 Point Database

    • Point 9 – 0100, Units x 1kBtu • Point 10 – 0050, Units x XMBtu 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 34 NOTE: Also refer to the Siemens’ Application Note, Document No. 140-0280 for additional information. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 35: Commissioning

    A worksheet for checking off these steps and recording measured values is located on the following page. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 36 BTU meter certificate of calibration. Record the temperature. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 37 End of standard commissioning. Please contact ONICON at (727)447-6140 with any questions. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 38 BTU meter certificate of calibration and the network, where appropriate. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 Page...
  • Page 39 98° F to 102° F (36.6° C to 38.9° C). This test confirms the operation of the BTU computer board input circuitry for temperature measurement. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 40 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 41 System-10-P1 units or multipliers are changed. For technical assistance, contact ONICON at (727) 447-6140. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 42 BTU METER ANALOG OUTPUTS BOARD (with 4 analog outputs) A-18 CONDITIONS OF SALE 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 Page...
  • Page 43 TYPICAL SYSTEM-10 INSTALLATION ONICON 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 1...
  • Page 44 For System-10 Btu Meter Shown with Temperature Sensor SUPPLY SIGNAL (RED) REFERENCE (BLACK) S/N 123456 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 2...
  • Page 45 THERMOWELL INSTALLATION ONICON 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 3...
  • Page 46 The thermowell could also be damaged or break apart causing a break in the water seal with the resultant loss of large amounts of water. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 47 HOT TAP THERMOWELL ASSEMBLY FOR BTU METERS ONICON 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 5...
  • Page 48 STANDARD INSTALLATION DETAIL FOR THERMOWELL ONICON In Welded Pipe 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 6...
  • Page 49 STANDARD INSTALLATION DETAIL FOR ONICON HEAVY DUTY THERMOWELL In Welded Pipe 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 7...
  • Page 50 STANDARD TEMPERATURE SENSOR ASSEMBLY ONICON For the System-10 Btu Meter 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 8...
  • Page 51 * Signal (Red) Return temperature * Reference (Black) Sensor * Shield 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 9...
  • Page 52 SYSTEM-10 BTU METER MOTHER BOARD ONICON Insertion Turbine Flow Meter Input Connections 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 1 0...
  • Page 53 SYSTEM-10 BTU METER MOTHER BOARD ONICON Insertion Electromagnetic Flow Meter Input Connections 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 1 1...
  • Page 54 SYSTEM-10 BTU METER MOTHER BOARD ONICON F-2500 Vortex Flow Meter Input Connections 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 1 2...
  • Page 55 F-2600 & F-2700 Vortex Flow Meter Input Connections 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 1 3...
  • Page 56 SYSTEM-10 BTU METER MOTHER BOARD ONICON Inline Electromagnetic Flow Meter Input Connections 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 1 4...
  • Page 57 ONICON F-3500 Insertion Electromagnetic Flow Meter Input Connections 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 1 5...
  • Page 58 ONICON FB-3500 Insertion Electromagnetic Flow Meter Input Connections 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 1 6...
  • Page 59 System-10 shield terminals and left unterminated at the flow meter. 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320...
  • Page 60 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 www.onicon.com • customerservice@onicon.com 0398-5 07-10 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 1 8...
  • Page 61 PROG MODE ENABLE DEVICE ADDRESS PROGRAM ENABLE SERIAL COMM 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 1 9...
  • Page 62 240 VAC - 1/8 Amp Slo-Blo, 3AG Fuse Not Used 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 2 0...
  • Page 63 SYSTEM-10 BTU METER P1 BOARD ONICON 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 2 1...
  • Page 64 ONICON P1 Board with Optional Digital Input Pulse (Di3) 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 2 2...
  • Page 65 DELTA T BTU RATE LO TEMP HI TEMP 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 2 3...
  • Page 66 SYSTEM-10 BTU METER ANALOG OUTPUTS BOARD ONICON with 4 analog outputs 11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • sales@onicon.com System-10-P1 Manual 09/15 - 0656-11 / 18320 A - 2 4...