SYSTEM-30 BTU MEASUREMENT SYSTEM
BACnet MS/TP Version
Installation and Operation Guide
For Software Version FB5.20 or higher.
1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727)442-5699
www.onicon.com • sales@onicon.com
01-09
0691

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SYSTEM-30 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Onicon SYSTEM-30

  • Page 1 SYSTEM-30 BTU MEASUREMENT SYSTEM BACnet MS/TP Version Installation and Operation Guide For Software Version FB5.20 or higher. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727)442-5699 www.onicon.com • sales@onicon.com 01-09 0691...
  • Page 2 Messages identified as “Important Note” contain information critical to the proper operation of the product. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691...
  • Page 3: Table Of Contents

    4.7.1 Diagnostic Lights ..................28 4.8 Commissioning ......................29 4.8.1 Commissioning Worksheet ................30 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691 Page 3...
  • Page 4 WIRING DIAGRAM SIGNAL CONNECTION BOARD WIRING DIAGRAM FOR DIN CONNECTOR BACnet BOARD 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691 Page 4...
  • Page 5: Introduction

    1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 www.onicon.com • sales@onicon.com 0333-2 01-13-09 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691 Page 5...
  • Page 6: Standard Features And Specifications

    Note: Specifications are subject to change without notice. Mode (Heating-Cooling) Indicator BAUD RATE 76800, 38400, 19200, or 9600 bps 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691 Page 6...
  • Page 7: Working Environment

    1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691...
  • Page 8: Unpacking

    NPT threads. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691...
  • Page 9: Installation

    For example, do not install the System-30 or its temperature sensor where it will be difficult for personnel to perform periodic maintenance and calibration. When selecting a site for mounting the system components, consider the criteria under Section 1.4, WORKING ENVIRONMENT, as well as the...
  • Page 10: Mechanical Installation

    1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691...
  • Page 11: Thermowell Installation

    Altering the cable length will affect calibration. Do not change the cable length without consulting ONICON. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691...
  • Page 12 THERMOWELL INSTALLATION IN THREADED PIPE TEES THERMOWELL INSTALLATION IN COPPER TEE 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691 Page 12...
  • Page 13: Electrical Installation

    In dual mode (2 pipes) applications the polarity of the temperature differential (Delta t) reverses; often on a seasonal basis. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691...
  • Page 14 (Supply Temp > Return Temp) Mode 2 Total Cooling (Supply Temp < Return Temp) 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691 Page 14...
  • Page 15 (Supply Temp > Return Temp) NORMALLY CLOSED CONTROL SYSTEM BACnet MS/TP NETWORK 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691 Page 15...
  • Page 16: Electrical Wiring

    Meter and the user’s external equipment. ONICON assumes no responsibility for damaged caused tot he external equipment as a result of an improper installation. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691...
  • Page 17: Start Up & Commissioning

    Successively pressing the SCROLL button will cycle the display through the run mode pages summarized in the tables on the next page. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691...
  • Page 18: Units And Multipliers

    The units and multipliers are programmed prior to delivery. Contact ONICON’s technical support personnel for assistance in changing units or multipliers. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691...
  • Page 19: Network Device Address Entry

    Btu meter and re-discover the device on the network. NETWORK ADDRESS DIP SWITCH VALUES SWITCH VALUE 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691 Page 19...
  • Page 20 DEVICE DIP SWITCH SETTINGS ADDRESS 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691 Page 20...
  • Page 21 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691 Page 21...
  • Page 22 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691 Page 22...
  • Page 23 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691 Page 23...
  • Page 24 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691 Page 24...
  • Page 25 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691 Page 25...
  • Page 26: Baud Rate

    The standard Baud rate settings are 9600, 19200, 38400 and 76800 Baud. If the Baud rate setting was not provided to ONICON, the Btu meter will be configured to “auto” detect the Baud rate of the network. In this configuration, the meter should detect and automatically adjust to the proper rate when the meter is connected to the network.
  • Page 27: Bacnet Objects

    4.6 BACnet OBJECTS The System-30 BTU Meter operates in one of two operating modes, SINGLE or DUAL. The table below contains point information for each of the operating modes. In SINGLE mode operation only one register accumulates energy and one register accumulates volume.
  • Page 28: Diagnostics

    This LED will flash at a rate that is proportional to the liquid flow rate. An unlit LED indicates no flow signal. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691...
  • Page 29: Commissioning

    ONICON’s technical support department to discuss specifics of your application In order to proceed with the following steps, the System-30 must be operating and connected to the control sys- tem. There must also be flow in pipes. Flow signal readings should be taken while holding the flow rate constant...
  • Page 30: Commissioning Worksheet

    Press and release switch S-1 to reset the Btu meter. For technical assistance, contact ONICON Incorporated at (727) 447-6140. 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691...
  • Page 31 WIRING DIAGRAM SIGNAL CONNECTION BOARD WIRING DIAGRAM FOR DIN CONNECTOR BACnet BOARD 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 - 0691 Page 31...
  • Page 35 1 2 3 4 5 6 7 8 1 2 3 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 A - 4...
  • Page 36 System-30 Signal Connection Board 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 A - 5 1500 North Belcher Road, Clearwater, Florida 33765 Tel (727) 447-6140 Fax (727) 442-5699 www.onicon.com E-mail: sales@onicon.com...
  • Page 38 System-30 MS/TP Board Baud rate MAC address dip switches dip switches RX LED TX LED 1500 North Belcher Road, Clearwater, FL 33765 • Tel (727) 447-6140 • Fax (727) 442-5699 • sales@onicon.com System-30 BTU Measurement System BACnet MS/TP 01/09 A - 7...