Chapter 3
Installing a Cisco Nexus 7009 Chassis
Figure 3-11
1
NRTL listed 45-degree grounding lug
Use the crimping tool to crimp the lug to the grounding wire. Verify that the ground wire is securely
Step 3
attached to the ground lug by attempting to pull the wire out of the crimped lug.
Remove the adhesive label from one of the two system grounding pads, and secure the grounding wire
Step 4
lug to the grounding pad with two M4 screws.
the front side of the chassis. Ensure that the grounding lug and the grounding wire do not interfere with
other switch hardware or rack equipment.
OL-23069-07
Inserting the Grounding Wire in the Grounding Lug
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
Grounding the Cisco Nexus 7009 Chassis
2
Grounding cable with 0.75 in. (19 mm) of insulation
stripped from the end
Figure 3-12
shows the location of the grounding pads on
3-21