Mounting Holes, Piping And Electrical Knockout Locations & Dimensions; Reversing Drain Pan Slope - Daikin AVV Installation And Maintenance Manual

Classroom unit ventilators floor models digital ready, microtec control (“j” vintage) field controls by others
Hide thumbs Also See for AVV:
Table of Contents

Advertisement

Mounting Holes, Piping and
Electrical Knockout Locations &
Dimensions
Figure 26: Front View with End Panels - Mounting Holes
Locations
Mounting Holes
13"
(330mm)
13"
(330mm)
6-1/2"
(165mm)
Size 07 = 48" (1219mm)
6-1/2"
(165mm)
Size 10 = 60" (1524mm)
Size 13 = 72" (1828mm)
Size 15 = 84" (2133mm)
Figure 27: Rear View without End Panels and Subbase -
Piping and Electrical Knockout Locations and Dimensions
8"
(203mm)
2-7/16"
(62 mm)
8"
Knockout Opening Between Pipe
(203mm)
2-7/16"
Tunnel & End Compartment.
(62 mm)
Rear Entry Area or Draftstop
Opening Knockouts
Outdoor Air Intake Opening
NOTICE
End compartment Draftstop knockouts must be removed for
proper Draftstop operation. (21-7/8" units only)
Note: See Draftstop IM bulletin (IM 473) for suggested
installation procedure.

Reversing Drain Pan Slope

Figure 28: Condensate Drain Pan Connection Location
Left Hand
7/8"(22 mm)
O.D. Drain
11"
(279 mm)
Front V iew of End Compartment
(Without End Panels)
www.DaikinApplied.com
1" (25 mm)
7" (178 mm)
7-1/4" (184 mm)
7-1/4" (184 mm)
(356mm)
14"
(356mm)
(127 mm)
5"
(127 mm)
Right Hand
7/8"(22 mm)
Condensate
O.D. Drain
Drain
4-3/4"
(121 mm)
11"
(279 mm)
Disconnect all electrical power before servicing unit to prevent
injury or death due to electrical shock.
Personal injury hazard. Wear protective gloves to avoid possible
cuts and abrasions from exposed edges. Avoid contact with
sharp edges.
Procedure
If the unit has a cooling coil, check the condensate drain
1" (25 mm)
pan to be sure it slopes down toward the drain stub-up
7" (178 mm)
end. To do so, compare the right and left hand drain pan
ends to
Figure 30
with the shallow lower bracket
is the low end of the drain pan. To reverse the slope of
the drain pan do the following:
Remove the lower bracket and upper plate from each
1 .
end of the unit, as shown in
on page
14. This is done by removing the screws
in each with a 1/4 inch nut driver.
14"
Reinstall the brackets on the opposite end of the unit.
2 .
21"
(533mm)
21"
(533mm)
5"
The drain pan has two (2) connections on each end; a standard
5" (127 mm)
drain connection and an overflow connection.
5" (127 mm)
Verify the standard drain connection is open on the
3 .
low (drain) end only. If the drain connection stub-outs
at the high end of the drain pan are open, seal them
water tight with silicone sealer or similar.
Mount static equalizer cover to low end bracket of
4 .
drain pan.
Figure 29: Mount Static Equalizer Cover
Deep
Upper
Bracket
Static
Equalizer
Cover
13
DANGER
CAUTION
&
Figure 31 on page
14. The end
(Figure 30 on page
Figure 30
and
NOTICE
14)
Figure 31
Coil
Connections
Drain Pan
Shallow
Lower
Bracket
IM 817-7