Check, Test & Start Procedure For: Daikin Applied Unit Ventilators - Daikin AVV Installation And Maintenance Manual

Classroom unit ventilators floor models digital ready, microtec control (“j” vintage) field controls by others
Hide thumbs Also See for AVV:
Table of Contents

Advertisement

Warranty Registration Form
Check, Test & Start Procedure For:
Daikin Applied Unit Ventilators
Note:
This form must be completely filled out and returned to, Daikin Warranty Department within ten days in order to comply with the terms of the Daikin Applied
warranty. Forms should be returned to Daikin Applied Warranty Department, P.O. Box 920, Auburn, NY 13021-0920.
Sales Office: ___________________________________S.O.#: _______________________ Date Started: _______________
Job Name: _____________________________________________G.O. # __________________________________________
Job Location: ___________________________________________________________________________________________
Unit Location: ____________________________ Unit Tagging: __________________________________________________
Model No: ________________________________ Serial No.: __________________________________________________
Supply Voltage: L1/L2 __________ L2/L3 __________
Room Fan Motor Amps:
T1: __________ RPM _________
I . Initial check
A. Does electrical service correspond to unit nameplate? ................................................................................. Yes 
B. Are all electrical power connections tight? ................................................................................................... Yes 
C. Does all field wiring conform to unit electrical schematic? ........................................................................... Yes 
D. Is unit installed per IM bulletin? .................................................................................................................... Yes 
F. Cabinet paint O.K.? ...................................................................................................................................... Yes 
G. Cabinet bent? ............................................................................................................................................... Yes 
H. Do outdoor (AEQ, AED, AZS, AZQ & AZR) and indoor fans turn freely? ..................................................... Yes 
I. Are all setscrews on outdoor and indoor fan couplings tight? ...................................................................... Yes 
J. Are end bearing bolts on outdoor and indoor fan shaft tight? ....................................................................... Yes 
K. Have the fan shaft end bearing and room fan motor been oiled (if applicable)? .......................................... Yes 
L. Are outdoor air and return air dampers operating properly? ......................................................................... Yes 
M. Is the filter clean? ......................................................................................................................................... Yes 
N. Is there excessive noise or vibration? . ........................................................................................................ Yes 
If Yes, corrective action (if any) ______________________________________________________________________________
© 2016 Daikin Applied • www.DaikinApplied.com • (800) 432–1342
L3/L1 ___________
Rated: _____________________________
Nameplate Rating: ___________________________
Form 573882Y
Group: Unit Ventilato®
Document PN: 573882Y
Date: June 2016
No 
No 
No 
No 
No 
No 
No 
No 
No 
No 
No 
No 
No 
Form 573882Y (06/16)