Nominal Range: 200 A
Measurement Range: 0.5 to 240 A AC
Transformation Ratio: 1000:1
Output Signal: 1 mA/A on 1
Accuracy and Phase Shift*:
Accuracy: 0.5 to 10 A: 3.0% Reading ± 0.5 A
10 to 40 A: 2.5% Reading ± 0.5 A
40 to 100 A: 2.0% Reading ± 0.5 A
100 to 240 A: 1.0% Reading ± 0.5 A
Phase Shift:
0.5 to 10 A: Not Specified
10 to 40 A: ≤ 5°
40 to 100 A: ≤ 3°
100 to 240 A: ≤ 2.5°
(*Reference conditions:18°C to 28°C, 20 to 75% RH,
external magnetic field < 40 A/m, 48 to 65 Hz sine
wave, distortion factor less than 1%, no DC
component, no external current carrying conductor,
test sample centered.) Load impedance 1.
Overload: 240 A for 10 min ON, 30 min OFF
Frequency Range: 40 to 10 kHz