AEMC MA114 User Manual

AEMC MA114 User Manual

Ac current probe

Advertisement

Quick Links

MA114
AC CURRENT PROBE
ENGLISH
User Manual

Advertisement

Table of Contents
loading

Summary of Contents for AEMC MA114

  • Page 1 MA114 ■ AC CURRENT PROBE ENGLISH User Manual...
  • Page 2 Serial #: 2153.41 Catalog #: MA114 Model #: Please fill in the appropriate date as indicated: Date Received: Date Calibration Due: Chauvin Arnoux ® , Inc. d.b.a AEMC ® Instruments www.aemc.com AC Current Probe Model MA114...
  • Page 3: Table Of Contents

    MODEL MA114 ..............7 2. OPERATION ....................8 2.1. MEASUREMENT PRINCIPLE ..............8 2.2. OPERATION .................... 8 2.2.1. CONNECTING THE MA114 ............. 8 2.2.2. DISCONNECTING THE MA114 ............. 10 2.2.3. AUTOMATIC POWER OFF ............10 2.3. EXTERNAL POWER (OPTIONAL) ............10 3.
  • Page 4 ® Thank you for purchasing the AEMC MiniFlex MA114 flexible current sensor. For best results from your instrument: read these operating instructions carefully comply with the precautions for use WARNING, risk of DANGER! The operator must refer to these instructions whenever this danger symbol appears.
  • Page 5: Precautions For Use

    PRECAUTIONS FOR USE The MA114 is protected against voltages up to 600 V with respect to earth in measurement category IV, or 1000 V in category III. The protection assured by the current sensor can be compromised if it is used in a way that is not recommended by the manufacturer.
  • Page 6: Receiving Your Shipment

    Ordering Information ® MiniFlex 14” Model MA114 (3A/1V/A, 30A/100mV/A, 300A/10mV/A, 3000A/1mV/A) ............Cat #2153.41 Includes two 1.5 V batteries (AA or LR6), multilingual safety data sheet, user manual, and verification certificate. AC Current Probe Model MA114...
  • Page 7: Description

    ≥ 1 MΩ. ® 1.2. MINIFLEX MODEL MA114 ® MiniFlex MA114 single‑phase 14” (35 cm) sensor converts alternating currents ranging from 3 to 3000 A into proportional AC voltages. Banana plugs (2), 0.16” (4 mm) diameter Flexible coil Sensor opening...
  • Page 8: Operation

    2. OPERATION 2.1. MEASUREMENT PRINCIPLE The MA114 sensor is based on the Rogowski coil principle. This provides: very good linearity and no saturation effect (and therefore no overheating) wide measurement dynamic, up to several kA insensitivity to DC (measurement of the AC component of any AC + DC...
  • Page 9 To optimize measurement, center the conductor in the coil. Set the switch to the range providing the best sensitivity and ensure the red OL indicator is off. (OL indicates saturation of the electronics, resulting in a measurement error.) AC Current Probe Model MA114...
  • Page 10: Disconnecting The Ma114

    While this feature is activated, the orange Auto Power Off indicator is lit. To override automatic power off: With the MA114 OFF, press and hold down the Auto Power Off button while turning the sensor ON by turning the switch to any measurement setting.
  • Page 11 1000 V CAT III or 600 V CAT IV. That makes it possible to safely connect the instrument to wattmeters with uninsulated inputs. The type B micro‑USB connector must not be in contact with conductors or uninsulated material at dangerous voltages. AC Current Probe Model MA114...
  • Page 12: Specifications

    , see the graph in § 3.5. The peak value is limited only by the electronics of the measurement unit (red OL indicator on). The coil alone can briefly withstand higher peak factors with no risk of overheating or damage. AC Current Probe Model MA114...
  • Page 13: Variations In The Range Of Use

    600 V between the jacket Common mode rejection 100 dB 80 dB and the secondary Input impedance of the 0.1% 10 kΩ to 1 MΩ measuring instrument 3.4. TYPICAL FREQUENCY RESPONSE GRAPHS 3.4.1. AMPLITUDE ERROR 3.4.2. PHASE ERROR AC Current Probe Model MA114...
  • Page 14: Typical Frequency Response Graphs

    3.6. POWER SUPPLY 3.6.1. BATTERIES The MA114 is powered by two 1.5 V alkaline batteries (type AA or LR6). The nominal operating voltage is between 1.8 and 3.2 V. The mean battery life is: 300 hours in continuous operation 1,800 10‑minute measurements...
  • Page 15: Environmental Conditions

    1: Range of reference 2: Operating range 3: Storage range (without battery) If the MA114 will be unused or stored for an extended period, remove its batteries. The sensor by itself can withstand a maximum temperature of 194°F (90°C) for 10 minutes.
  • Page 16: Conformity To International Standards

    Electrical safety per IEC 61010‑2‑032 for type B sensors. Double insulation Measurement category: IV Rated voltage: 600 V (or 1000 V in CAT III) 3.10. ELECTROMAGNETIC COMPATIBILITY (CEM) Emissions and immunity in an industrial environment per IEC 61326‑1. AC Current Probe Model MA114...
  • Page 17: Maintenance

    4. MAINTENANCE Except for the batteries, the MA114 contains no parts that can be replaced by personnel who have not been specially trained and accredited. Any unauthorized repair or replacement of a part by an “equivalent” may significantly impair safety.
  • Page 18: Warranty

    WARRANTY Your AEMC instrument is warranted to the owner for a period of two years from the date of original purchase against defects in manufacture. This limited ® warranty is given by AEMC Instruments, not by the distributor from whom it was purchased.
  • Page 19 NOTES: AC Current Probe Model MA114...
  • Page 20 05/19 99-MAN 100494 v1 Chauvin Arnoux ® , Inc. d.b.a. AEMC ® Instruments 15 Faraday Drive • Dover, NH 03820 USA Phone: (603) 749-6434 • Fax: (603) 742-2346 www.aemc.com...