Installation Instructions Original Instructions 5069 Compact I/O EtherNet/IP Adapters Catalog Numbers 5069-AENTR, 5069-AEN2TR Topic Page Summary of Changes About the Adapters Install a 5069 Compact I/O System Set the Network Internet Protocol (IP) Address Install the Adapter onto the DIN Rail Connect Power to the 5069-AEN2TR Adapter Connect Power to the 5069-AENTR Adapter Connect the Adapter to an EtherNet/IP Network...
Page 2
5069 Compact I/O EtherNet/IP Adapters ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration and operation of this equipment before you install, configure, operate or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
Page 3
5069 Compact I/O EtherNet/IP Adapters Environment and Enclosure ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in EN/IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.
Page 4
5069 Compact I/O EtherNet/IP Adapters WARNING: Special Conditions for Safe Use: • This equipment is not resistant to sunlight or other sources of UV radiation. • This equipment shall be mounted in an ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (as defined in EN/IEC 60529) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments.
5069 Compact I/O EtherNet/IP Adapters WARNING: • If you connect or disconnect wiring while the field-side power is on, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. •...
5069 Compact I/O EtherNet/IP Adapters Install a 5069 Compact I/O System • The adapter is the left-most component in the bank. • Local 5069 Compact I/O modules are installed to the right of Before you install the adapter, verify that you have the following: the adapter.
Page 7
5069 Compact I/O EtherNet/IP Adapters Adapter Dimensions 5069-AENTR Adapter Dimensions 59.56 mm 5069-AEN2TR Adapter Dimensions (2.34 in.) 101.66 mm 56.00 mm (4.00 in.) (2.20 in.) 98.10 mm (3.86 in.) 143.97 mm 139.00 mm (5.67 in.) (5.47 in.) 123.00 mm 123.00 mm 132.40 mm 137.84 mm (4.84 in.)
5069 Compact I/O EtherNet/IP Adapters Set the Network Internet Protocol (IP) Address System Power Considerations 5069 Compact I/O EtherNet/IP adapters provide power to a 5069 5069 Compact I/O EtherNet/IP adapters ship DHCP-enabled and Compact I/O system via RTBs that are connected to external power with their rotary switches set to 000.
5069 Compact I/O EtherNet/IP Adapters At powerup, the adapter reads the rotary switches to determine if they 2. If the DIN rail latches are open, gently push the rear latch back are set to a valid number for the last octet of the IP address. If the until the front latch pops up and clicks.
Page 10
5069 Compact I/O EtherNet/IP Adapters 1. Verify that the external power supply is not powered. Install the MOD Power RTB 2. Strip insulation from the wires that you connect to the RTB. WARNING: If you connect or disconnect the Removable Terminal RTB Type Action Block (RTB) with power applied, an Electric Arc can occur.
Page 11
5069 Compact I/O EtherNet/IP Adapters 3. Connect the DC(+) wire from the external DC power supply Install the SA Power RTB to the first + terminal. WARNING: If you connect or disconnect the Removable Terminal RTB Type Action Block (RTB) with power applied, an Electric Arc can occur. This 1.
Page 12
5069 Compact I/O EtherNet/IP Adapters 4. Connect the L2/N/AC(—) wire from the external SA AC power source to the first — terminal. symbol denotes an earth ground terminal that provides a low impedance path between electrical circuits and RTB Type Action earth for functional purposes and provides noise immunity 1.
5069 Compact I/O EtherNet/IP Adapters Connect Power to the 5069-AENTR Adapter Connect MOD Power to the 5069-AENTR Adapter Before you connect an external power source to the Power RTB Before you connect MOD power or SA power to a 5069-AENTR terminals that are used for MOD power, make sure that the power adapter, complete the following tasks: source is properly sized.
Page 14
5069 Compact I/O EtherNet/IP Adapters 4. Connect the 24V DC(—) wire from the external power supply 4. Connect the DC(—) wire from the external SA DC power to the — terminal. supply to the —/N terminal. RTB Type Action RTB Type Action 1.
Page 15
5069 Compact I/O EtherNet/IP Adapters Connect SA AC Power to the 5069-AENTR Adapter 5. Connect a wire from an earth ground location to the terminal on the RTB. Before you connect an external power source to the Power RTB terminals that are used for SA power, make sure that the power source RTB Type Action is properly sized.
5069 Compact I/O EtherNet/IP Adapters Connect the Adapter to an EtherNet/IP Network Install the End Cap Use an RJ45 straight cable to connect the adapter to an EtherNet/IP A 5069-ECR end cap is shipped with the adapter. network. You must install an end cap on the right side of the last module in a 5069 Compact I/O system.
5069 Compact I/O EtherNet/IP Adapters Remove or Replace the Adapter 3. Remove the RTBs: ATTENTION: Do not remove or replace a Terminal Base unit while power is applied. Interruption of the ATTENTION: Do not remove or replace an adapter while power is backplane can result in unintentional operation or applied.
5069 Compact I/O EtherNet/IP Adapters Specifications This table includes a subset of specifications for the adapter. For full specifications, see the 5069 Compact I/O Modules Specifications Technical Data, publication 5069-TD001. Attribute 5069-AEN2TR 5069-AENTR Temperature, operating 0 °C < Ta < +60 °C •...
EtherNet/IP Embedded Switch Technology Application Guide, publication ENET-AP005 Allen-Bradley® EtherNet/IP devices that are equipped with embedded switch technology. EtherNet/IP Media Planning and Installation Manual Describes how to use the required media components and provides information on how to plan for, install, This manual is available from the Open DeviceNet Vendor Association (ODVA) at verify, troubleshoot, and certify your EtherNet/IP network.
Page 20
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page. Allen-Bradley, Compact I/O, Logix5000, Rockwell Automation, Rockwell Software, RSLinx, and Studio 5000 Logix Designer are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.