Refrigerant Line Routing - Ecoer 2436 Installation Instructions Manual

Inverter split heat pump, up to 20 seer, 2-3-4-5ton capacity, r410a
Hide thumbs Also See for 2436:
Table of Contents

Advertisement

ESI Outdoor Unit Installation Instruction

5. Refrigerant Line Routing

Comply with National, State, and Local Codes when isolating line sets from joists, rafters, walls, or
other structural elements. Take precautions to prevent noise within the building structure due to
vibration transmission from the refrigerant lines. For Example:
• Use isolation type hangers when the refrigerant lines have to be fastened to floor joists or other framing.
• Isolation hangers should also be used when refrigerant lines traverse stud spaces or enclosed ceilings.
• Where the refrigerant lines pass through a wall or sill, it should be insulated and isolated.
• Isolate the lines from all ductwork.
• Minimize the number of 90º turns.
Side View
Secure suction line from joists using isolators every 8 ft. Secure liquid line directly to insulated
suction line using tape, wire, or other appropriate method every 8 ft.
Side View
Secure suction line using isolators every 8 ft. Secure liquid line directly to insulated suction line
using tape, wire, or other appropriate method every 8 ft.
Sealant
Wall
Figure 5-3 Isolation through wall
Manufacturer reserves the right to change specifications or designs without notice.
8 Feet Maximum
8 Feet Maximum
Figure 5-1 Isolation from Joist/Rafter
8 Feet Maximum
Figure 5-2 Isolation in wall spaces
Insulation
Suction line
9/31
8 Feet Maximum
Figure 5-4 DO NOT hang line sets from ductwork
www.ecoer.com
Isolator
Joist/Rafter
Line Set
Isolator
Wall
Line Set
Isolator
Ductwork
Line Set
08.2018