Troubleshooting Chart - McQuay Suite Incremental Installation & Maintenance Data

Ptac/pthp conditioner
Table of Contents

Advertisement

TROUBLE
1. Blowers won't operate on
COOL.
2. Blowers operate on COOL
but compressor doesn't
start.
3. Blowers run on COOL and
compressor starts but
stops after a short
interval.
4. Blowers run on COOL and
compressor starts and
runs, but compressor
occasionally stops (on
overload device).
5. Compressor starts and
runs on COOL but blowers
do not run.
6. Compressor starts and
runs on COOL but blowers
do not run.
7. Equipment gives electrical
shock.
8. Insufficient cooling
capacity.
IM 368 / Page 14 of 20 (Rev 11/03)

Troubleshooting Chart

These items should be checked by a qualified service techician only.
CAUSE
a. No power.
b. Faulty pushbutton switch.
c. Loose connections at pushbutton switch.
a. Thermostat set too high.
b. Heat valve is open and heat is on.
c. Low voltage.
d. Fault pushbutton switch.
e. Faulty connection at pushbutton switch.
f.
Defective wiring to thermostat.
g. Loose connections at compressor terminals.
h. Wiring to compressor terminals defective.
i.
Loose connections in compressor overload device.
j.
Starting capacitor malfunctions (open circuited, short
circuited or loss of capacity.
k. Defective compressor motor (short circuited, open
circuited, grounded).
a. Operation of overload device due to overloading
compressor motor.
a. Low voltage due to overloaded circuits within building or
throughout the local power system. Due to varying
power demands, this condition might exist only at
certain times during the day or on very hot days.
b. High voltage due to fluctuations in local power system;
usually occurs at low load periods of the day.
c. Partial short circuit in compressor motor. Under normal
loading a compressor with a partial short circuit might
appear to be operating all right; increased condensing
air temperature might then cause a short.
a. Faulty pushbutton switch.
b. Open circuited blower motor.
c. Blower rubbing against its housing.
d. Bearings on blower motor seized.
e. Loose connection at pushbutton switch.
a. Operation of the internally connected overload device
due to a short circuit in blower motor.
b. Windings, rubbing of blower wheel or lack of lubrication
in blower motor bearings.
a. Grounded electrical circuit.
a. Equipment standing too long without being run.
b. Insufficient airflow through condenser due to:
1) Dirty condenser.
2) Obstructed louvers on outer cabinet or wall box.
3) Condenser blower/fan not running.
4) Condenser blower/fan not up to speed.
5) Condenser blower/fan slipping on motor shaft.
6) Recirculation of condenser air.
c. Insufficient airflow through evaporator due to:
1) Dirty evaporator.
2) Ice on evaporator coils.
3) Dirty air filter.
4) Obstructed discharge grilles.
5) Evaporator blower motor not running.
6) Evaporator blower motor not up to speed.
7) Evaporator blower slipping on motor shaft.
d. Heat load in room exceeds capacity of equipment.
e. Windows and doors in room are open.
f.
Compressor not pumping, indicated by:
1) Low wattage.
2) Condenser not warm, evaporator only partially cool
or not at all.
CURE
a. Check supply line fuses, circuit breakers, and be sure the
power is on. Blown fuses would indicate circuit overload-
ing, a short circuit, or a grounded condition in the circuit.
Voltage supply to the equipment should be checked.
Voltage must be within 10% of voltage given on data
plate.
b. Replace.
c. Tighten.
a. Adjust. Rotate control knob to "Cooler."
b. Close heat valve.
c. Check as above.
d. Replace.
e. Tighten.
f.
Replace.
g. Tighten.
h. Replace.
i.
Tighten.
j.
Replace.
k. *Ship cooling chassis prepaid to nearest McQuay authorized
warranty station.
a. Check voltage supply. Clean condenser inside and out. Check
at outside face of condenser for recirculation of condenser air.
Put air "splitters" in, if missing. Check to make sure condenser
blower/fan is operating properly. Check compressor for short
circuit. If defective, *ship cooling chassis to nearest McQuay
authorized warranty station.
a. Run separate electric line to equipment. Consult local power
company.
b. Consult local power company.
c. If confirmed, ship cooling chassis prepaid to nearest McQuay
authorized warranty station.
a. Replace.
b. Replace.
c. Adjust blower motor or blower wheel position.
d. Replace motor
e. Tighten.
a. Adjust blower/fan wheel on shaft or blower motor mounting.
b. Adjust blower wheel or motor or replace wheel.
a. Eliminate ground.
a. If the air conditioner is allowed to stand for an extended
length of time without being run on COOL, it is possible for all
the refrigerant to become absorbed in the oil inside the
compressor and refrigeration circuit. If this should happen,
there will be no cooling until the necessary working pressures
have been established. This will take about 5 minutes of
continuous running.
b.
1) Clean.
2) Remove obstructions.
3) Check same as in the case of malfunctioning con-
ditioner air blower.
4) Check for correct voltage. Oil blower motor if nec-
essary.
5) Adjust blower position and tighten setscrew.
6) Correct as in No. 3 above.
c.
1) Clean.
2) Turn equipment off to let ice melt.
3) Clean or replace.
4) Remove obstructions. In case of top discharge equipment,
make sure books, magazines, etc., are kept off the
equipment.
5) Check as in No. 1.
6) Check for correct voltage.
7) Adjust motor wheel position and tighten setscrew.
d. Refer to original load calculations; recalculate heat load.
e. Close therm.
f.
*Ship prepaid to nearest McQuay authorized warranty station.
Continued on next page

Advertisement

Table of Contents
loading

Table of Contents