Remotec ZTS-110 User Manual page 8

Z-thermostat
Hide thumbs Also See for ZTS-110:
Table of Contents

Advertisement

Step
Procedure / Description
Press "Prog" key once to confirm the setting
and it will go to minutes setting.
4
Minutes will keep flashing, press Up/Down
key to set minutes.
Press "Prog" key once to confirm the setting
and it will go to 12/24 hour clock selection.
5
Press Up/Down key to toggle the 12/24
hour clock selection.
Press "Prog" key once to confirm the setting
and it will go to temperature F (Fahrenheit)
-> C (Celsius) selection.
6
Press Up/Down key to toggle the
temperature F (Fahrenheit) -> C (Celsius)
selection.
Press "Prog" key once to confirm the setting
and it will go to swing setting.
7
Press Up/Down key to set the swing setting.
o
o
o
o
(Range is from 0.5 C to 2 C or 1 F to 4 F )
Press "Prog" key once to confirm the setting
and it will go to differential set point setting.
8
Press Up/Down key to set the differential set
o
o
point setting. (Range is from 0.5 C to 2 C or
o
o
1 F to 4 F )
13
LCD indication
Step
MO
AM
9
AM
PM
HR
10
Note: Explanations of Swing and Differential set point
HEAT mode: thermostat controls the temperature according to the following
Output
SWING
Off
MO
Example for Heating: (Set point = 70 F, Swing = 1 F, Differential = 2 F)
=> 1st stage heater turns on when room temp is 69 F and off at 71 F.
DIFF
=> 2nd stage heater turns on when room temp is 67 F and off at 70 F.
Procedure / Description
Press "Prog" key once to confirm the setting
and it will go to Advanced Recovery setting.
RECOVERY
Press Up/Down key to enable/disable
Advanced Recovery Mode.
RECOVERY
MO
Press "Prog" key once to confirm the setting
PROG ON
and it will go to the Home page.
diagram
Set point
nd
nd
2 Turn on
2 Turn off
Heat
st
st
1 Turn on
1 Turn off
Diff
Swing
Swing
o
o
14
LCD indication
WAKE
AM
OFF
FAN AUTO
Temperature
SD= switch differential
o
o
o
o
o

Advertisement

Table of Contents
loading

Table of Contents