L M T S E R I E S | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R | O I/ L M T 1 0 0/ 2 0 0 - E N R E V. B
Menu: Device Setup (continued)
Menu/Parameter
Device Setup/Write Protect
Software WP
Hardware WP
Device Setup/PV Setup
PV Unit
PV LRV
PV URV
PV Damping Time
Device Setup/Device
Variables/Level
Level Units
Lower Range
Upper Range
PV Offset
Device Setup/Device
Variables/Interface
Lower Range
Damping Time
Upper Range
Interface Offset
Device Setup/Device
Variables/Temperature
Lower Range
Upper Range
Temperature Offset
Lower Temp Limit
Upper Temp Limit
Value Range
On, Off
Unlocked, Locked
• Unit length
- mm, cm, m, in, ft
• Unit volume
- Liters, Cubic meters, cubic inches, cubic feet, cubic
yards, gallons, Imperial gallons, bushels, barrels,
liquid barrels
• Unit flow
- Liters/second, liters/minute, liters/ hour, gallons/
second, gallons/minute, gallons/hour, gallons/day,
imperial gallons/ second, imperial gallons/minute,
imperial gallons/ hour, imperial gallons/day,
barrels/ second, barrels/minutes, barrels/ hour,
barrels/day, cubic meters/second, cubic meters/
minute, cubic meters/hour, cubic meters/day, cubic
feet/second, cubic feet/minute, cubic feet/hour,
cubic feet/day
• Non linearized
- Minus 20% to 120% of probe length
• Linearized
-999999999 to 999999999
• Non linearized
- Minus 20% to 120% of probe length
• Linearized
-999999999 to 999999999
0.1 – 60 seconds
mm, cm, m, in, ft
• Non linearized
- Minus 20% to 120% of probe length
• Linearized
-999999999 to 999999999
• Non linearized
- Minus 20% to 120% of probe length
• Linearized
-999999999 to 999999999
+/- 50% of probe length
• Non linearized
- Minus 20% to 120% of probe length
• Linearized
-999999999 to 999999999
0.1-60 seconds
• Non linearized
- Minus 20% to 120% of probe length
• Linearized
-999999999 to 999999999
+/- 50% of probe length
C, F
–200°C to 300°C
–200°C to 300°C
–200°C to 300°C
–200°C to 300°C
–200°C to 300°C
Description
Sets ability of user to edit parameters through software
Sets ability of user to edit parameters through
mechanical switch on the top of the trasmitter housing
Defines unit of measure for primary variable
Sets 4 mA output point which is also the lower range
value of the measuring span
Sets 20 mA output point which is also the upper range
value for the measuring span
Allows signal smoothing of the 4-20 mA signal.
Sets units for level output type
select temperature unit of measure
35