L M T S E R I E S | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R | O I/ L M T 1 0 0/ 2 0 0 - E N R E V. B
Error Message
Tx LCD Message
S224.043
Primary Current
Saturated
_156.025
Electronics NV
Syncing
C154.047
Sensor Config
Warning
C200.019
Device Reset
Required
C211.018
Sensor Board NV
Write Error
F098.001
Temperature Sensor
Failure
F194.031
Sensor Board Fault
F196.020
Sensor
Communication
Failure
F198.000
Level Sensor Failure
F212.017
Sensor Board
Memory Failure
Possible Cause
Current saturated high or low
Write non-volatile command
received from CB
Non-volatile Storage in
progress
The Level sensor trim is set to
a default value
The Temperature trimming
configuration is corrupted
Device change requires restart
An attempt to save data to the
sensor module has failed
A temperature measurement
has resulted in a value outside
of the operating range
An error occurred in the sensor
module Possible causes could
be a failed component in the
sensor electronics, a
configuration error, or the
sensor assembly
An error occurred in the
communication between the
sensor and electronics
modules
An error occurred in the sensor
module Possible causes could
be a failed component in the
sensor electronics or an error
changing the configuration
Writing to the sensor non-
volatile memory was not
successful
Suggested Action
Check process conditions and/or device
configuration The compatibility of level
transmitter model and process conditions has to
be checked Probably a different transmitter type
is required
Information only
Contact service to perform a factory level sensor
trim
Restart device
Restart the device If the condition persists
contact service
Restart the device If the condition persists
contact service for a replacement
Using a HART configurator (DTM - Hand held) or
the local HMI, navigate to the Diagnostics ->
Waveform display and confirm the quality of the
signal The signal peak should visibly cross the
threshold line and should measure approximately
2 Volts. Contact ABB service for additional
support or a replacement if the condition
persists
Restart the device If the condition persists
contact service for a replacement
Restart the device If the condition persists
contact service for a replacement
The sensor should be replaced as soon as
possible
65
Tx Response
No effect
No effect
No effect
No effect
No effect
Analog signal to alarm
Analog signal to alarm
Analog signal to alarm
Analog signal to alarm
Analog signal to alarm