L M T S E R I E S | M A G N E TO S T R I C T I V E L E V E L T R A N S M I T T E R | O I/ L M T 1 0 0/ 2 0 0 - E N R E V. B
Menu: Easy Setup (continued)
Menu/Parameter
Easy Setup
Language
Set PV
PV Unit
PV LRV
PV URV
PV Damping Time
Display 1 Line 1 View
Tag
Value Range
English, Chinese, Portuguese, German, Spanish, French,
Italian
Level, Interface, Distance/Ullage, Volume Level, Volume
Interface, Flow
• Unit length
- mm, cm, m, in, ft
• Unit volume
- Liters, Cubic meters, cubic inches, cubic feet, cubic
yards, gallons, Imperial gallons, bushels, barrels,
liquid barrels
• Unit flow
- Liters/second, liters/minute, liters/hour, gallons/
second, gallons/minute, gallons/hour, gallons/day,
imperial gallons/ second, imperial gallons/minute,
imperial gallons/hour, imperial gallons/day, barrels/
second, bar rels/minutes, barrels/hour, bar rels/day,
cubic meters/second, cubic meters/minute, cubic
me ters/hour, cubic meters/day, cubic feet/second,
cubic feet/ minute, cubic feet/hour, cubic feet/day
Non linearized
Minus 10% to half of probe length
Linearized
-999999999 to 999999999
Non-linearized
Half to 20% beyond probe length
Linearized
-999999999 to 999999999
0.1 - 60 seconds
Level, Interface, Distance/Ullage
alphanumeric
Description
Menu language options
Select device variable where applicable which will be
assigned to the 4-20 mA output and HART primary
variable
Defines unit of measure for primary variable
Sets 4 mA output point which is also the lower range
value of the measuring span
Sets 20 mA output point which is also the upper range
value for the measuring span
Allows signal smoothing of the 4-20 mA signal.
Select variable to be viewed on display
User defined. 32 characters available.
33