Install Piping To Control; Install Control - Honeywell VR8205 Installation Instructions Manual

Direct ignition combination gas controls
Hide thumbs Also See for VR8205:
Table of Contents

Advertisement

Complete the instructions below for installing the piping,
installing the control, connecting the pilot gas tubing and
the wiring. Make sure the leak test you perform on the
control after completing the installation includes leak
testing the adapters and screws. If you use a wrench on
the valve after the flanges are installed, use the wrench
only on the flange, not on the control. See Fig. 5.
Location
The gas controls are mounted in the appliance vestibule
on the gas manifold. If this is a replacement application,
mount the gas control in the same location as the old
control.
Locate the combination gas control where it cannot be
affected by steam cleaning, high humidity, or dripping
water, corrosive chemicals, dust or grease accumulation
or excessive heat. To assure proper operation, follow
these guidelines:
• Locate gas control in a well-ventilated area.
• Mount gas control high enough above cabinet bottom
to avoid exposure to flooding or splashing water.
• Assure the ambient temperature does not exceed the
ambient temperature rating for each component.
• Cover gas control if appliance is cleaned with water,
steam or chemicals or to avoid dust and grease
accumulation.
• Avoid locating gas control where exposure to corrosive
chemical fumes or dripping water is likely.

Install Piping to Control

All piping must comply with local codes and ordinances or
with the National Fuel Gas Code (ANSI Z223.1, NPFA No.
54), whichever applies. Tubing installation must comply
with approved standards and practices.
1. Use new, properly reamed pipe that is free from
chips. If tubing is used, make sure the ends are
square, deburred and clean. All tubing bends must
be smooth and without deformation.
2. Run pipe or tubing to the control. If tubing is used,
obtain a tube-to-pipe coupling to connect the tubing
to the control.
3. Install a sediment trap in the supply line to the
control. See Fig. 3.

Install Control

1. Mounted 0 to 90 degrees in any direction, including
vertically, from the upright position of the gas control
knob.
2. Mount so the gas flow is in the direction of the arrow
on the bottom of the control.
3. Thread the pipe the amount shown in Table 7 for
insertion into control or adapters. Do not thread
pipe too far. Valve distortion or malfunction can
result if the pipe is inserted too deeply.
VR8105, VR8205, AND VR8305 DIRECT IGNITION COMBINATION GAS CONTROLS
Table 7. NPT Pipe Thread Length (in.).
Pipe
Thread Pipe
Size
this Amount
3/8
9/16
1/2
3/4
3/4
13/16
DROP
PIPED
HORIZONTAL
GAS
SUPPLY
GAS
CONTROL
3 IN.
(76 MM)
MINIMUM
2
DROP
HORIZONTAL
TUBING
GAS
1
SUPPLY
RISER
3 IN.
(76 MM)
MINIMUM
2
ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.
1
2
CAUTION: SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING
END CAP TO PREVENT GAS FROM FILLING THE WORK AREA. TEST
FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.
Fig. 3. Sediment trap installation.
4. Apply a moderate amount of good quality pipe com-
pound (do not use Teflon® tape) only to the pipe,
leaving two end threads bare. On LP installations,
use a compound resistant to LP gas. See Fig. 4.
5. Remove the seals over the control inlet and outlet if
necessary.
6. Connect the pipe to the control inlet and outlet. use
a wrench on the square ends of the control. If a
flange is used, place the wrench on the flange
rather than on the control. Refer to Fig. 5 and 6.
TWO IMPERFECT
THREADS
GAS CONTROL
PIPE
THREAD PIPE THE AMOUNT
SHOWN IN TABLE FOR
INSERTION INTO GAS CONTROL
Fig. 4. Use moderate amount of pipe compound.
5
Maximum Depth Pipe can be
inserted into Control
3/8
1/2
3/4
RISER
PIPED
GAS
SUPPLY
3 IN.
(76 MM)
MINIMUM
2
GAS
CONTROL
APPLY A MODERATE AMOUNT OF
PIPE COMPOUND TO PIPE ONLY
(LEAVE TWO END THREADS BARE).
69-1226—04
GAS
CONTROL
M3077
M3075B