Continuous pilot combination gas control

Advertisement

Quick Links

These continuous pilot gas controls are used in gas-fired
appliances with capacities up to 300 feet
pressure drop [5.7 meters
They include a manual valve, safety shutoff, two automatic
operators, a pressure regulator, pilot adjustment, and a con-
duit cover. See Table 1 for temperature ranges and regulator
types.
BODY PATTERN: Straight-through body pattern.
CAPACITY:
Inlet x Outlet
Size (In.)
1/2 X 1/2
1/2 X 3/4
3/4 X 3/4
a
Capacity based on 1000 Btu/feet
gravity natural gas at 0.25 kPa pressure drop].
TABLE 1—TEMPERATURE RANGES AND
REGULATOR TYPES.
Ambient
Model
Temperature
Number
Range
VR4300A
0° F to 175° F
[-18° C to +79° C]
VR4300C
0° F to 175° F
[-18° C to +79° C]
VR4300H
0° F to 175° F
[-18° C to +79° C]
VR4300M
-40° F to 175° F
[-40° C to +79° C]
VR4300P
-40° F to 175° F
[-40° C to +79° C]
Combination Gas Control
3
/hour at one inch wc
3
/hour at 0.25 kPa] on natural gas.
Capacity at 1 inch wc
a
Pressure Drop
3
180 feet
/hour
3
[5.1 meter
/hour]
3
190 feet
/hour
3
[5.4 meter
/hour]
3
200 feet
/hour
3
[5.7 meter
/hour]
3
, 0.64 specific gravity natural gas at 1 inch wc pressure drop [37.3 MJ/meter
Regulator
Type
Standard-opening
Step-opening
Slow-opening
Standard-opening
Step-opening
T.H. • Rev. 3-93 • © Honeywell Inc. 1993 • Form Number 69-0683—1
Continuous Pilot
INLET X OUTLET SIZES AVAILABLE: 1/2 by 3/4 inch
and 3/4 by 3/4 inch.
ADAPTERS: Adapters available for 1/2 and 3/4 inch straight
and angle connections. Refer to Table 2.
ELECTRICAL RATINGS:
Voltage and Frequency: 120 Vac, 60 Hz.
Current Draw: 0.14A.
Use conversion factors in Table 3 to convert capacities for
other gases.
Minimum
Regulated Capacity
3
30 feet
/hour
3
[0.8 meter
/hour]
3
30 feet
/hour
[0.8 meter 3 /hour]
3
30 feet
/hour
3
[0.8 meter
/hour]
TABLE 2—ADAPTER (FLANGE) PART NUMBERS.
Inlet/
Outlet
Pipe Size
1/2 inch NPT
3/4 inch NPT
NOTE: Flange kits include one flange with attached O-ring
and fan mounting screw.
TABLE 3—GAS CAPACITY CONVERSION
Gas
Manufactured
Mixed
Propane
APPROVALS:
American Gas Association design certificate: UP-70-57A.
Canadian Gas Association design certificate: 1029-CC-8375.
VR4300
Application
Maximum
Regulated Capacity
3
225 feet
/hour
3
[6.4 meter
/hour]
3
290 feet
/hour
3
[8.2 meter
/hour]
3
300 feet
/hour
3
[8.5 meter
/hour]
3
Part Number
Without
Flange
Hex
Type
Wrench
Straight
393690-6
Elbow
393690-3
Straight
393690-4
Elbow
393690-5
FACTORS.
Specific
Multiply Listed
Gravity
Capacity By
0.60
0.70
1.53
, 0.64 specific
With
Hex
Wrench
393690-16
393690-13
393690-14
393690-15
0.516
0.765
1.62

Advertisement

loading

Summary of Contents for Honeywell VR4300

  • Page 1 Multiply Listed Gravity Capacity By Manufactured 0.60 0.516 Mixed 0.70 0.765 Propane 1.53 1.62 APPROVALS: American Gas Association design certificate: UP-70-57A. Canadian Gas Association design certificate: 1029-CC-8375. T.H. • Rev. 3-93 • © Honeywell Inc. 1993 • Form Number 69-0683—1...
  • Page 2: Installation

    Installation To convert a gas control from natural gas to LP gas or from LP gas to natural gas, contact your Honeywell representative. WHEN INSTALLING THIS PRODUCT… Convert standard- or slow-opening gas controls from 1. Read these instructions carefully. Failure to follow...
  • Page 3 control by following the same precautions and instruc- 5. Remove seals over gas control inlet and outlet if tions that are used for installing the gas control. After the necessary. adapter is installed, attach the gas control to the adapter as 6.
  • Page 4 Fig. 5—Proper use of wrench on gas control. WHEN FLANGE IS NOT USED WHEN FLANGE IS USED APPLY WRENCH APPLY WRENCH TO FLANGE ONLY FROM TOP OR BOTTOM OF GAS CONTROL TO EITHER SHADED AREA M3083 Connect Pilot Gas Tubing Connect Thermocouple 1.
  • Page 5 Fig. 7—Installing thermocouple to the power unit. Fig. 8—Wiring connections for 120 volt control. THERMOCOUPLE 120V LEAD THERMOSTAT HIGH LIMIT CONTROLLER (HOT) GAS CONTROL TERMINALS POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. DO NOT JUMPER THESE TERMINALS. THIS SHORTS VALVE COIL AND MAY BURN OUT ANTICIPATOR IN THERMOSTAT.
  • Page 6: Start-Up And Checkout

    Start-up and Checkout ADJUST THE PILOT BURNER FLAME The pilot flame should envelop 3/8 to 1/2 inch [10 to 13 millimeters] of the thermocouple tip. Refer to Fig. 9. To WARNING adjust the pilot flame: 1. Remove the pilot adjustment cover screw. Refer to FIRE OR EXPLOSION HAZARD CAN Fig.
  • Page 7: Check Safety Shutdown Performance

    Standard-Opening and Slow-Opening Pressure Regulator pressure using a manometer connected to the gas control 1. The gas control outlet pressure should match the outlet pressure tap. Refer to Fig. 4. manifold pressure listed on the appliance nameplate. 3. If necessary, adjust the pressure regulator to match 2.
  • Page 8: Maintenance

    Maintenance CAUTION Do not apply a jumper across or short the valve WARNING coil terminals. This may burn out the heat antici- pator in the thermostat. FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE IMPORTANT: Allow 60 seconds after shutdown before INJURY, OR DEATH re-energizing step-opening model to assure lightoff Improper cleaning or reassembly may cause gas...
  • Page 9 INSTRUCTIONS TO THE HOMEOWNER 1. Set the thermostat to its lowest setting. 2. Disconnect all electric power to the appliance. 3. Remove the gas control access panel. WARNING 4. Push in the gas control knob slightly and turn clock- wise to OFF.
  • Page 10 Home and Building Control Home and Building Control Helping You Control Your World Honeywell Inc. Honeywell Limited—Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley, Minnesota 55422 Scarborough, Ontario M1P 2V9 QUALITY IS KEY Printed in U.S.A.