Power Supply - AEMC 8500 User Manual

Digital transformer ratiometer
Table of Contents

Advertisement

Available languages

Available languages

CT Test Mode Ready
Indicates system ready for CT testing
X Circuit: OPEN (or CONT)
Refer to the VT/PT Continuity Test section
H Circuit: OPEN (or CONT)
Refer to the VT/PT Continuity Test section
Low X Signal
Check X cables for inadvertent short circuits.
X winding may be shorted or transformer circuit breaker may be open.
Low H Signal
Check H cables for inadvertent short circuits.
Check H cable connector at DTR
front panel.
®
4.6

Power Supply

The DTR
Model 8500 may be used for up to 10 hours on fully charged
®
NiCd batteries. The DTR
may also be line supplied during measurements.
®
In this mode the DTR
also recharges the NiCd batteries.
®
LOW BATTERY is displayed when the internal batteries approach low
voltage. When displayed, a limited number of measurements may still
be conducted, though we recommend recharging the DTR
as soon as
®
possible. If the battery voltage drops too low, the DTR
will lock out further
®
operation. In the lock-out mode, the DTR
shuts down all functions until
®
AC power is applied and the battery recharged.
We recommend recharging the DTR
overnight. Each time the DTR
is
®
®
connected to AC power, a 14-hour recharge cycle begins. Repeat charging
of partially discharged batteries will not result in battery damage. During
the 14-hr cycle, the CHARGING indicator will glow continuously; following
this period, a pulse-trickle charge mode is entered and the indicator will
pulse on and off.
17
Digital Transformer Ratiometer DTR
Model 8500
®

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

Table of Contents