Wiring And Mounting - Mitsubishi Electric FX2N-64DP-M Hardware Manual

Profibus-dp master block, melsec-f
Table of Contents

Advertisement

FX2N-64DP-M Profibus-DP Master Block
2.

Wiring and Mounting

Caution
1) Do not lay signal cable near to high voltage power cable or house them in the same
trunking duct. Effects of noise or surge induction may occur. Keep signal cables a safe
distance of more than 100 mm (3.94") from these power cables.
2) Ground the shield wire or the shield of a shielded cable at one point on the programmable
controller. Do not, however, ground to the same point as high voltage lines.
3) Terminal screws of the 64DP-M are M3 (0.12"), therefore crimp style terminals (see
drawing) suitable for use with these screws should be fitted to the cable for wiring.
Figure 2.1: Crimp Terminals
6.2 mm (0.24" )
or less
4) The terminal tightening torque is 0.5
5) Cut off all phases of power source before installing / removing or performing wiring work on
the master in order to avoid electric shock or damage of product.
6) Replace the provided terminal cover before supplying power and operating the unit after
installation or wiring work, in order to avoid electric shock.
For M3 (0.12")
6.2 mm (0.24")
ž
~
0.8 N
For M3 (0.12")
or less
m. Tighten securely to avoid malfunction.
Wiring and Mounting 2
2-1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx2n

Table of Contents