Mitsubishi Electric FX2N-64DP-M Hardware Manual page 32

Profibus-dp master block, melsec-f
Table of Contents

Advertisement

FX2N-64DP-M Profibus-DP Master Block
Table 3.3: Performance Specifications
Item
POWER LED
RUN LED
SD / RD LED
LED
indicators
TOKEN LED
READY LED
FROM/TO LED
PRM.SET LED
RSP ERR LED
LED
FAULT LED
indicators
TEST LED
STATION LED
ON when 24V DC power is supplied form the PLC or external power
supply.
ON: During normal operation
OFF: Error
Flashes during communication with slave on the Profibus network.
The flashing interval is the time interval of the bus parameter's Data
Control Time.
ON when token is maintained.
ON when the Profibus-DP network subscription preparation is
completed and during subscription.
ON when a FROM/TO instruction from the programmable controller
is operating.
ON (PARAMETER SET) when in the parameter setting mode. When
flashing during normal operation, the parameter is not written.
ON when a communication error occurs.
ON when an error occurs.
ON when self-diagnosis is executing.
Displays the station address during normal operation.(Binary)
Displays the test type during a self-diagnosis. (B0 to B6)