I/O SIGNAL LIST
6.2.5

I/O signal when CC-Link Ver.2 octuple setting is selected (Pr. 544 = 18)

(1) Remote I/O (32 points)
Same as when Pr. 544 = 0 (
(2) Remote resister
Description
Address
Upper 8 Bits
RWwn
Monitor code 2
RWwn+1
Set frequency (0.01Hz increments)
Link parameter
RWwn+2
expansion setting
RWwn+3
RWwn+4
Monitor code 3
RWwn+5
Monitor code 4
RWwn+6
Monitor code 5
RWwn+7
Monitor code 6
Alarm definition
RWwn+8
No.
RWwn+9
PID set point (0.01% increments)
RWwn+A
PID measured value (0.01% increments)
RWwn+B
PID deviation (0.01% increments)
RWwn+C
Torque command
RWwn+D
RWwn+E
RWwn+F
*1
When Pr. 128 = "50, 51, 60, 61", they are valid.
*2
Setting "3" or "5" in Pr.804 during torque control under real sensorless vector control or vector control makes
torque command valid. (FR-A700 series only)
50
Refer to page 44)
Refer
Lower 8 Bits
Page
Monitor code 1
Instruction code
Write data
H00
*1
*1
*1
*2
H00 (Free)
to
Address
Upper 8 Bits
60
RWrn
60
RWrn+1
61
RWrn+2
Reply code 2
61
RWrn+3
61
RWrn+4
61
RWrn+5
61
RWrn+6
61
RWrn+7
Alarm definition
61
RWrn+8
62
RWrn+9
Alarm definition (output frequency)
62
RWrn+A
Alarm definition (output current)
62
RWrn+B
Alarm definition (output voltage)
76
RWrn+C
Alarm definition (energization time)
RWrn+D
RWrn+E
RWrn+F
Description
Lower 8 Bits
First monitor value
Second monitor value
Reply code 1
Read data
Third monitor value
Fourth monitor value
Fifth monitor value
Sixth monitor value
Alarm definition
No.
data
H00 (Free)
Refer
to
Page
64
64
64
64
65
65
65
65
65
65
65
65
65