Monitor Codes - Mitsubishi FR-A7NC Instruction Manual

Inverter plug-in option cc-link communication function
Table of Contents

Advertisement

7.2.4

Monitor codes

Monitor items selected with RWw0, RWw4 to 7 are explained below.
Devide the monitor code (RWw0) into half to select the first monitor description (RWr0) from the lower 8
bits and the second monitor description (RWr1) from the upper 8 bits.
REMARKS
When Pr. 544 = 12, 14, 18, (114, 118) descriptions of monitor code 3 (RWw4) to 6 (RWw7) can be selected.
(Example) When output current is selected for the first monitor and running speed is selected for the
second monitor → monitor code is H0602
Code
Second Monitor Description
Number
(the first 8 bits)
H00
Output frequency
H01
H02
H03
H05
H06
H07
H08
H09
H0A
H0B
H0C
H0D
H0E
H0F
H10
H11
First, Third to Sixth Monitor Description
*1, *11
Output frequency
Output current
Output voltage
Set frequency
Running speed
Motor torque
Converter output voltage
Regenerative brake duty
Electronic thermal relay function load factor
Output current peak
Converter output voltage peak
Input power
Output power
Input terminal status
Output terminal status
Load meter
(the last 8 bits)
No monitoring (monitor value is 0)
*1, *11
*1
*3
*4
*6
*7
DETAILS OF INPUT AND
OUTPUT SIGNALS
Increments
0.01Hz
0.01Hz
0.01A / 0.1A
0.1V
0.01Hz
1r/min / 0.1r/min
0.1%
0.1V
0.1%
0.1%
0.01A / 0.1A
0.1V
0.01kW / 0.1kW
0.01kW / 0.1kW
0.1%
*2
*12
*2
7
*2
*2
73

Advertisement