Mitsubishi FR-A7NC Instruction Manual page 52

Inverter plug-in option cc-link communication function
Table of Contents

Advertisement

Device
No
RY(n+1)0
to
Reserved
RY(n+1)7
RY(n+1)8 Not used
(initial data process completion flag)
Not used
RY(n+1)9
(initial data process request flag)
RY(n+1)A Error reset request flag
RY(n+1)B
to
Reserved
RY(n+1)F
("n" indicates a value determined according to the station number setting.)
*1
Signal names are initial values. Using Pr. 180 to Pr. 186, Pr. 188, and Pr .189, you can change input signal functions.
Signals of the RYn0, RYn1, and RYn9 can not be changed. Even when changed using Pr. 178, Pr. 179, and Pr. 187,
the settings are invalid.
Refer to the inverter manual (applied) for details of Pr. 178 to Pr. 189.
*2
Signal names are initial values. Using Pr. 190 to Pr .196, you can change output signal functions.
Refer to page 58 for signals which can be assigned.
*3
Output signal can be assigned using Pr. 313 to Pr. 315.
Refer to page 58 for signals which can be assigned.
Refer
Signal
Page
Device
to
No
RX(n+1)0
to
Reserved
RX(n+1)7
RX(n+1)8 Not used
(initial data process request flag)
Not used
RX(n+1)9
(initial data process completion flag)
55
RX(n+1)A Error status flag
RX(n+1)B Remote station ready
RX(n+1)C
to
Reserved
RX(n+1)F