DETAILS OF INPUT AND
OUTPUT SIGNALS
(2) Alarm data
Refer to the inverter manual for details of alarm definitions.
Data
Definition
H00
No alarm
H10
OC1
H11
OC2
H12
OC3
H20
OV1
H21
OV2
H22
OV3
H30
THT
H31
THM
H40
FIN
H50
IPF
H51
UVT
H52
ILF
H60
OLT
H70
BE
H80
GF
H81
LF
H90
OHT
*1
Displayed only on the FR-A700 series.
*2
Appears only when the FR-A7AP is mounted.
72
Data
Definition
H91
PTC
HA0
OPT
HA1
OP1
HA3
OP3
*1
HB0
PE
HB1
PUE
HB2
RET
HB3
PE2
HC0
CPU
HC1
CTE
HC2
P24
HC4
CDO
HC5
IOH
HC6
SER
HC7
AIE
HC8
USB
*1
HD0
OS
*1, *2
HD1
OSD
*1, *2
Data
Definition
HD2
ECT
Alarm definition display example
*1, *2
HD3
OD
(instruction code H74)
*1, *2
HD5
MB1
*1
HD6
MB2
*1
HD7
MB3
*1
HD8
MB4
*1
HD9
MB5
*1
HDA
MB6
*1
HDB
MB7
*1
HDC
EP
*1, *2
HF1
E.1
HF2
E2
*1
HF3
E3
*1
HF6
E.6
HF7
E.7
HFB
E11
*1
HFD
E.13
For read data H30A0
b15
b8 b7
0
0
1 0 0 0 0
0
0
1
1
1
Last alarm
Current alarm
(H30)
(HA0)
Last alarm ...... THT
Current alarm ...... OPT
b0
0
0
0
0