vacon • 31
2.3.12

Group PID-controller: Menu Par G12

Code
P12.1
P12.2
P12.3
P12.4
P12.5
Feedback minimum
P12.6
Feedback maximum
P12.7
PID controller P gain
P12.8
PID controller I-time
P12.9
PID controller D-time
P12.10
Error value inversion
P12.11
P12.12
P12.13
P12.14
P12.15
Sleep setpoint boost
P12.16
P12.17
P12.18
Sleep loss check time
NOTE!
This group is hidden when PID output is not used as frequency reference.
2
Parameter
Min
Setpoint source
0
PID setpoint 1
0.0
PID setpoint 2
0.0
Feedback source
0
0.0
10.0
0.0
0.00
0.00
0
PID error limit
0.0
Sleep frequency
0.00
Sleep time delay
0
Wake-up limit
0.0
0.0
Sleep boost time
0
Sleep max loss
0.0
1
Table 17. PID controller parameters.
Defau
Max
Unit
ID
lt
3
0
332
100.0
%
50.0
167
100.0
%
50.0
168
4
0
334
50.0
%
0.0
336
300.0
%
100.0
337
1000.0
%
100.0
118
320.00
s
10.00
119
10.00
s
0.00
132
1
0
340
100.0
%
100.0
1812 Limit on error
P1.2
Hz
0.00
1016
3600
s
30
1017
100.0
%
5.0
1018
50.0
%
10.0
1815 Referred to setpoint
60
s
10
1816 Boost time after P12.13
50.0
%
5.0
1817 Referred to feedback after boost
300
s
30
1818 After boost time P12.16
Description of Groups
Description
0 = PID setpoint 1/2
1 = AI1
2 = AI2
3 = Fieldbus
Fixed setpoint 1
Fixed setpoint 2
0 = AI2
1 = AI1
2 = Fieldbus
3 = AI2- AI1
4 = Temperature (OPTBH)
Value at minimum signal
Value at maximum signal
If the value of the parameter is
set to 100% a change of 10% in
the error value causes the con-
troller output to change by 10%.
If this parameter is set to 1,00
second a change of 10% in the
error value causes the control-
ler output to change by 10.00%/
s.
If this parameter is set to 1,00
second a change of 10% in the
error value during 1.00 s causes
the controller output to change
by 10.00%.
0 = Normal (Feedback < Setpoint
-> Increase PID output)
1 = Inverted (Feedback < Set-
point -> Decrease PID output)
Drive goes to sleep mode when
the output frequency stays
below this limit for a time
greater than that defined by
parameter P12.13.
The minimum amount of time
the frequency has to remain
below the Sleep level before the
drive is stopped.
Defines the level for the PID
feedback value wake-up.