Section 10
Testing functionality by secondary injection
10.1.4
76
A new recording begins. The view is updated if you leave the menu and
return.
1.2. Navigate to General information or to Trip values to obtain more
detailed information.
2.
Open the Disturbance handling tool for the IED in the plant structure in
PCM600.
2.1. Right-click and select Execute manual Trig in the window Available
recordings in IED.
2.2. Read the required recordings from the IED.
2.3. Refresh the window Recordings and select a recording.
2.4. Right-click and select Create Report or Open With to export the
recordings to any disturbance analyzing tool that can handle Comtrade
formatted files.
Evaluation of the results from the disturbance recording function requires access to
a PC either permanently connected to the IED or temporarily connected to the
Ethernet port (RJ-45) on the front. The PCM600 software package must be
installed in the PC.
Disturbance upload can be performed by the use of PCM600 or by any third party
tool with IEC 61850 protocol. Reports can automatically be generated from
PCM600. Disturbance files can be analyzed by any tool reading Comtrade
formatted disturbance files.
It could be useful to have a printer for hard copies. The correct start criteria and
behavior of the disturbance recording function can be checked when IED
protective functions are tested.
When the IED is brought into normal service it is recommended to delete all
recordings, made during commissioning to avoid confusion in future fault analysis.
All recordings in the IED can be deleted in two ways:
1.
in the local HMI under Main menu/Clear/Reset disturbances, or
2.
in the Disturbance handling tool in PCM600 by selecting Delete all recordings
in the IED... in the window Available Recordings in IED.

Event recorder (ER) and Event list (EL)

The result from the event recorder and event list can be viewed on the local HMI
or, after upload, in PCM600 as follows:
1.
on the local HMI under Main menu/Events, or in more details via
2.
the Event Viewer in PCM600.
The internal FIFO register of all events will appear when the event viewer is
launched.