The Lon Protocol; Hardware And Software Modules - ABB RER670 Commissioning Manual

Relion 670 series, railway application version 2.2 iec
Hide thumbs Also See for RER670:
Table of Contents

Advertisement

Section 7
Establishing connection and verifying the LON communication
7.1.2
7.1.3
54
The fiber optic LON bus is implemented using either glass core or plastic core fiber
optic cables.
Table 13:
Specification of the fiber optic connectors
Cable connector
Cable diameter
Max. cable length
Wavelength
Transmitted power
Receiver sensitivity

The LON Protocol

The LON protocol is specified in the LonTalkProtocol Specification Version 3
from Echelon Corporation. This protocol is designed for communication in control
networks and is a peer-to-peer protocol where all the devices connected to the
network can communicate with each other directly. For more information of the
bay-to-bay communication, refer to the section Multiple command function.

Hardware and software modules

The hardware needed for applying LON communication depends on the
application, but one very central unit needed is the LON Star Coupler and optical
fibers connecting the star coupler to the IEDs. To interface the IEDs from the
MicroSCADA with Classic Monitor, application library LIB520 is required.
The HV Control 670 software module is included in the LIB520 high-voltage
process package, which is a part of the Application Software Library in
MicroSCADA applications.
The HV Control 670 software module is used for control functions in the IEDs.
The module contains a process picture, dialogues and a tool to generate a process
database for the control application in MicroSCADA.
When using MicroSCADA Monitor Pro instead of the Classic Monitor, SA LIB is
used together with 670 series Object Type files.
The HV Control 670 software module and 670 series Object Type
files are used with both 650 and 670 series IEDs.
Use the LON Network Tool (LNT) to set the LON communication. This is a
software tool applied as one node on the LON bus. To communicate via LON, the
IEDs need to know
Glass fiber
ST-connector
62.5/125 m
1000 m
820-900 nm
-13 dBm (HFBR-1414)
-24 dBm (HFBR-2412)
1MRK 506 377-UEN C
Plastic fiber
snap-in connector
1 mm
10 m
660 nm
-13 dBm (HFBR-1521)
-20 dBm (HFBR-2521)
Railway application RER670 2.2 IEC
Commissioning manual
M14804-32 v2
M14804-35 v5

Advertisement

Table of Contents
loading

Table of Contents