Basic Procedure - Omron PRT1-COM Operation Manual

Profibus-dp multiple i/o terminal, gt1 series
Table of Contents

Advertisement

Basic Procedure

4-1
Basic Procedure
1
Determine the MULTIPLE
I/O TERMINAL I/O
specifications.
2
Select the I/O Units.
3
Check the specifications.
4
Mount and connect the
Communication Unit and
I/O Units.
5
Set the DIP switches for the
Communication Unit,
Analog Input Units, and
Analog Output Units.
6
Connect to the
PROFIBUS-DP Master Unit.
7
Turn ON the power.
8
Configure PROFIBUS-DP
system.
9
Check the operation.
38
The basic operating procedure is shown below. For details about settings and
connections, refer to PROFIBUS-DP Master Operation Manual (W349). For
explanations about Slave Units, refer to Section 6 Basic I/O Unit Specifications
and Section 7 Special I/O Unit Specifications.
Inputs:
Number of points/input type/connection type
Outputs:
Number of points/input type/connection type
Analog inputs:
Number of points
Analog outputs:
Number of points
Pulse Input (Counter): Number of points
Commu-
+
Transistor Input
nication
Terminal
Connec-
High-den
Unit (1)
block
tor
connector
16 points 16 points 32 points
Unit
Unit
The total current supplied from the Communication Unit to each I/O Unit (I/O Unit interface current
consumption) is 0.3 A max.
Mount Units on DIN rail (DIN 35-mm track: all Units).
Connect I/O Unit Connecting Cables and end connector.
Connect Communication Unit internal power supply (24 VDC --15%/+10%).
Connect I/O power supply (24 VDC --15%/+10%) for each Transistor Input/Output Unit and Relay
Output Unit.
Connect I/O power supply (24 VDC --15%/+10%) for each Analog Input/Output Unit and power
supply for each Counter Unit encoder, using a separate power supply from the above.
Connect I/O to each I/O Unit.
Set the PROFIBUS-DP address of the Communication Unit.
Set the Analog Input Unit and Analog Output Unit ranges and other specifications.
Connect the Communication Unit to the PROFIBUS-DP Master Unit using the PROFIBUS-DP
Communications Cable.
Turn ON the PC power supply.
Turn ON the I/O power supply to individual I/O Units.
Turn ON the Communication Unit internal power supply.
Configure all connected MULTIPLE I/O Units in de PROFIBUS-DP master.
Check the I/O Unit interface status.
Check the indicators on all Units.
The following indications are normal:
Communication Unit US indicator:
Communication Unit BF indicator:
TS indicators for I/O Units and Communicaton Unit: green ON
Check that the data for the I/O words allocated in the I/O memory of the CPU Unit of the PC is
being correctly read and written by the CPU Unit.
Transistor Output
+
Terminal
Connec-
High-den
sity
block
tor
sity
connecto
r
16 points 16 points 32 points
Unit
Unit
Unit
Unit
green ON
OFF
Section
Relay Output
+
Analog
Analog
Terminal
block
Input
Output
16 points
8 points
8 points 4 points
Unit
Unit
Unit
Unit
4-1
Counter
Input
1 points
Unit

Advertisement

Table of Contents
loading

Table of Contents