4.6 Wiring of the FP-FNS Blocks

4.6.1 FP-FNS Block PROFIBUS DP Wiring

Use a standard PROFIBUS cable and standard 9-pin Sub-D male PROFIBUS connectors.
We recommend using a straight (0°) bus interface connector (e.g. PR 103-658). When a
horizontal (90°) bus interface connector is used, the cables will be directed toward the top of
the unit, which may cause difficulties when installing other devices in a control cabinet.

4.6.2 FP-FNS Block DeviceNet Wiring

Open style connector/suitable wire
DeviceNet has a standard open style connector.
If additional connectors are needed, use the standard CAN 5-pin open style connectors
manufactured by Phoenix Contact.
No. of contacts
5
Terminal block for DeviceNet
For a suitable wire, please refer to cable selection (see page 40).
Wiring method
Attach a plug-in, open style connector to a cable.
1. Strip 65mm (2.6in.) to 75mm (3in.) of the outer jacket from the end of the cable,
leaving no more than 6.4mm (0.25in.) of the braided shield exposed.
Phoenix Contact product ID
Model no.
MSTB 2,5/ 5-ST-5,08 ABGY AU
Wiring of the FP-FNS Blocks
Product no.
1849037
41