Wiring - Panasonic CZ-64ESMC3 Installation Instructions Manual

System controller
Hide thumbs Also See for CZ-64ESMC3:
Table of Contents

Advertisement

Wiring

Power supply wiring
• Be sure to use a dedicated line for power source.
• Be sure to earth this controller.
• Do not connect the earth wiring to those of gas pipe, water pipe, lighting rod,
telephone, etc.
Type of wiring:
• Use a fl exible wiring of 2 mm
• Use the standard power supply wiring for Europe (such as H05RN-F or H07RN-F
which conform to CENELEC (HAR) rating specifi cations) or use the wiring based
on IEC standard (60245 IEC57, 60245 IEC66).
Total Wire Length: 30 m or less
Power supply terminal screw: M4
Inter-unit control wiring
Type of wiring:
• Use a fl exible shield
wiring of 0.5 to 2 mm
Total wire length:
• 1000 m or less
External I/O wiring
Type of wiring:
• Use a fl exible wiring of
0.5 to 2 mm
.
2
Total Wire Length:
• 100 m or less
Basic wiring diagram
Connect the inter-unit control wiring as shown in the fi gure.
When connecting interface adaptor, read the installation instructions supplied with each product.
Power Source
100-240V ~
Power suply
wiring
(Recommended).
2
Number of connectable units and devices:
(Up to total of 100 units and devices can be connected.)
.
2
Indoor unit
Outdoor unit
Central control device
(*1) The number of indoor units includes the interface adaptor.
Attention
When using the controller at a location susceptible
to noise, use a shield wiring.
System Controller
Up to 64 units (*1)
Up to 30 units
Up to 10 units
Inter-unit control wiring
• No polarity
11
(EN)

Advertisement

Table of Contents
loading

Table of Contents