Replacing The Remaining Peripheral Devices - Siemens FDOOT241-9 Technical Manual

Modernizing fire detection installations with multiple protocol detectors
Hide thumbs Also See for FDOOT241-9:
Table of Contents

Advertisement

4.2.2
Building Technologies
Fire Safety
Step 2: Replacing the control panel and changing over to FDnet protocol

Replacing the remaining peripheral devices

When changing over to the FDnet, all peripheral devices on a detector line which
have not been modernized must be replaced. This applies to the following device
groups in particular:
All special detectors
l
All manual call points
l
All input/output modules, input modules, output modules
l
Multi-T-Tap devices (DC1135, DC1157, SIGMALOOP splitter): The
l
FDCL221-M multi line separator module can be used for the conversion into
permissible FDnet topologies.
For MS8/PMT: The addressed display lights must be replaced with
l
addressable alarm indicators FDCAI221.
Peripheral devices which do not need to be replaced
The following base adapters can continue to be operated on the FDnet:
FDB241
l
FDB251
l
FDB299
l
The following Sinteso point detectors can continue to be operated with the relevant
base adapters when operated on the FDnet:
FDT2xx
l
FDO2xx
l
FDOOT2xx
l
The acoustic base DBZ1195A, the relay base DBC1191A-AA, and the humidity
base DBZ1192 can continue to be used with the same functions with the AlgoRex
DB11x1A bases and the FDB241, FDB251, and FDB299 base adapters.
The detector heating unit DBZ1190-A-AC, however, cannot continue to be used.
Undertaking modernization
A6V10323158_d_en_--
2015-04-09
4
27