Siemens FDOOT241-9 Technical Manual page 24

Modernizing fire detection installations with multiple protocol detectors
Hide thumbs Also See for FDOOT241-9:
Table of Contents

Advertisement

4
Undertaking modernization
Step 1: Detector modernization
24
Building Technologies
Fire Safety
Operation as
Selected parameter set in the
detector of type:
control panel configuration
DO1151A
APS005S
DO1152A
APS006S
APS007S, APS009S
DO1153A
APS073SH
APS070SH, APS071SH,
APS072SH
DOT1151A
APS083S²
DOT1152A
APS084S
APS005S, APS06S, APS015S,
APS019S, APS009S,
APS082S ³
APS007S, APS085S
APS081S
APS080S
DT1152A
APS100T
APS105T
APS103T
APS107T
¹ Does not meet the criteria of EN 54-7
² This parameter set is applied differently in the modes 'Manned' and 'Unmanned'
³ The static activation temperature is 80 °C in emulation mode instead of 70 °C for
the parameter set APS082S
You will find more information in documents 007227 and 009718.
See the chapter 'Applicable documents [➙ 7]'.
Active parameter set and emulation
mode on the detector
'OO' Universal mode (1)
'OO' Sensitive mode (3)
'OO' Super Sensitive mode (5)
'OO' Super Sensitive mode (5)
'OO' Ultra Sensitive mode (6)¹
Manned:
'OOT' High Suppression mode (8)¹
Unmanned:
'OOT' Balanced mode (4)
'OOT' Suppression mode (5)
'OOT' Balanced mode (4)
'OOT' Fast Response mode (6)
High Sensitive Fast 'OOT' mode (9)
'OOT' Super Sensitive mode (11)
'T' A1R mode (1)
'T' BR mode (2)
'T' A1S mode (3)
'T' BS mode (4)
A6V10323158_d_en_--
2015-04-09