Installer Setting - Emergency Heater Setting - LG PREMTB001 Owners And Installation Manual

New wide wired remote controller
Hide thumbs Also See for PREMTB001:
Table of Contents

Advertisement

INSTALLATION INSTRUCTION
76
Installer Setting – Emergency Heater Setting
This function is only available on some products
This function will set the Emergency Heater Setting.
Emergency Heater is used to heat the space in emergency case such as heat pump error.
Emergency heat is in place of and does not supplement heat pump.
C Emergency Heater setting Function sets following conditions:
1) Emergency Heater operation while in error or outdoor unit operates cooling cycle.
2) Emergency Heater operation in Low Ambient temperature
3) Fan speed setting during Emergency Heater operation
Setting2 : Low Ambient
Heating Operation
Setting3 : FAN Speed
Setting during Emergency
Heater Operation
!
CAUTION
This function setting must be carried out by a certified-technician.
Incorrect function setting can cause fire.
B
Press and hold
button for more than 3 seconds to enter the installer settings mode.
- If pressing only once briefly, it will enter the user settings mode.
Make sure to press and hold for more than 3 seconds.
Move to the Emergency Heater Setting in the menu using
Select the Emergency Heater Setting using F G button.
C If 00 is set at this stage, setting 2 & setting 3 will not be available.
❈ Set value for Function Setting
00 : not use
01 : use
Function Code
Setting1: Heater Operation while in error or
outdoor unit operates cooling cycle.
Setting1 : Heater
Operation while in error
or outdoor unit operates
cooling cycle.
B
button and then it displays as below.
Move to Low Ambient Heating Operation setting by pressing I button.
Press F G button to setup Low Ambient Heating Operation.
00: Not use
01~03: compressor on/off Setting step
01~15: compressor on/off Setting step(step expand indoor unit)
C Emergency heater operation in Low Ambient temperature
- compressor off : Emergency heater enabled
- compressor on : Emergency heater disabled
Move FAN Speed Setting during Emergency Heater Operation by pressing I button.
Press F G button to setup FAN Speed during Emergency Heater Operation.
0 : fan off
1 : fan on
K
Press
button to save.
L
Press
button to exit or system will automatically exit after 25 seconds without any input.