Page 1
37218D easYgen-300 Genset Control Operation Manual Software Version starting from 2.0008 Manual 37218D...
Page 2
Provides other helpful information that does not fall under the warning or caution categories. Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is believed to be correct and reliable. However, Woodward assumes no responsibility unless otherwise expressly undertaken.
Manual 37218D easYgen-300 Series - Genset Control Revision History Rev. Date Editor Change NEW 04-10-15 Release 05-12-14 Minor corrections; MCB closing limit description added; update to reflect version V2.0006 06-03-23 Minor corrections; wire size conversion chart added; update to reflect version V2.0007 (refer to Update In-...
Page 4
Manual 37218D easYgen-300 Series - Genset Control 7. O ................34 HAPTER PERATION AND AVIGATION Operation and Display ........................... 35 Purpose of the Status LEDs ......................35 Operating the easYgen ....................... 35 Acknowledging Alarm Messages ....................35 ...
Page 6
Manual 37218D easYgen-300 Series - Genset Control F. S ..................... 120 PPENDIX ERVICE PTIONS Product Service Options ........................120 Returning Equipment For Repair ......................120 Packing a Control ........................121 Return Authorization Number RAN ................... 121 ...
Manual 37218D easYgen-300 Series - Genset Control Chapter 1. General Information Related Documents ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Type English German easYgen-300 Series easYgen-300 – Manual this manual 37218 Additional Manuals LeoPC1 – User Manual 37146 GR37146 PC program for configuration, parameter visualization, remote control, data logging, language upload, alarm and user management, and event recorder management.
Page 11
Manual 37218D easYgen-300 Series - Genset Control The easYgen-300 Series generator set controller provides the following functions: • Genset control • Engine and generator protection • Engine data measurement - including oil pressure and temperature, coolant temperature, battery voltage, speed, service hours, etc.
Table 2-1: easYgen series 300 product features NOTE Some parameters of the easYgen-300 series can only be configured using the Direct Configuration Ca- ble DPC (P/N 5417-557) and a notebook/PC with the software LeoPC1. These parameters are indicated with an in the parameter description under Parameters starting from page 70 and can not be confi- gured at the unit directly.
CAUTION To prevent damage to electronic components caused by improper handling, read and observe the pre- cautions in Woodward manual 82715, Guide for Handling and Protection of Electronic Controls, Printed Circuit Boards, and Modules. NOTE The unit is capable to withstand an electrostatic powder coating process with a voltage of up to 85 kV and a current of up to 40 µA.
Manual 37218D easYgen-300 Series - Genset Control Installation ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ For installation into a door panel, proceed as follows: Panel cut-out Cut out the panel according to the dimensions in Figure 4-1. Remove terminals Loosen the wire connection terminal screws on the back of the unit and remove the wire connection terminal strips if required (1).
The control unit is capable of handling voltage drops to 0 V for a maximum of 10 ms. CAUTION Ensure that the engine will be shut down by an external device in case the power supply of the easYgen-300 control unit fails. Failure to do so may result in damages to the equipment. Charging Alternator ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡...
Figure 6-4 to Figure 6-12. NOTE Please note that not all measuring methods can be performed with all models of the easYgen-300 se- ries. The methods of measurement are indicated in the wiring diagrams for the respective models.
Manual 37218D easYgen-300 Series - Genset Control Voltage Measuring: Generator 1Ph 2W, [320], [320X], [350], [350X] Phase-Neutral Voltage Measuring Generator voltage 1Ph 2W Generator voltage 1Ph 2W easYgen 320 & 350 easYgen 320X & 350X Figure 6-7: Voltage measuring - generator 1Ph 2W, phase-neutral Phase-Phase Voltage Measuring It is also possible to perform a phase-phase voltage measuring.
Manual 37218D easYgen-300 Series - Genset Control Discrete Inputs ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Discrete Inputs: Bipolar Signals The discrete inputs are galvanically isolated allowing for a bipolar connection. The discrete inputs are able to handle positive or negative signals. NOTE All discrete inputs must use the same polarity, either positive or negative signals, due to the common ground.
Figure 6-18: Discrete inputs - alarm/control inputs - operation logic For the easYgen-300 series, the discrete inputs 1-3 are configured to a factory default and cannot be changed. The discrete inputs 4 and 5 are freely configurable depending on the parameter "Ignore CB reply". If this para- meter is set to "YES", the discrete inputs are freely configurable, and the operation logic may be configured ei-...
Manual 37218D easYgen-300 Series - Genset Control Relay Outputs ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The easYgen series 300 provides up to six (6) galvanically isolated relay outputs. Some relay outputs have fixed assignments and cannot be configured. max. 250 Vac/dc Relay output external device...
39/40 Table 6-10: Interfaces - connection overview NOTE The DPC cable (P/N 5417-557) is intended for service operation only. Do not operate the easYgen-300 with the DPC plugged into the unit during regular operation. NOTE The CAN interface is only used for the visualization of J1939 data from the ECU.
• Incorrect baud rate (too high) for length of CAN bus • The CAN bus cable is co-routed with power cables Woodward recommends the use of twisted-pair cables for the CAN bus (i.e.: Lappkabel Unitronic LIYCY (TP) 2×2×0.25, UNITRONIC-Bus LD 2×2×0.22).
Manual 37218D easYgen-300 Series - Genset Control Maximum CAN bus Length The maximum length of the communication bus wiring is dependent on the configured Baud rate. Refer to Table 6-11 for the maximum bus length (Source: CANopen; Holger Zeltwanger (Hrsg.); 2001 VDE VERLAG GMBH, Berlin und Offenbach;...
Manual 37218D easYgen-300 Series - Genset Control Chapter 7. Operation and Navigation Figure 7-1: Front panel and display Figure 7-1 illustrates the front panel/display which includes push-buttons, LEDs and the alphanumerical 7 seg- ment LED display. A short description of the front panel is given below.
Manual 37218D easYgen-300 Series - Genset Control Operation and Display ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Purpose of the Status LEDs The easYgen has several status LEDs to indicate the operating state. The LEDs indicate the following conditions: (on): Mains voltage present (only easYgen-350 and 350X)
Display of the Operating Values The easYgen-300 control units are able to display various measured values during operation depending on the re- spective easYgen model. You may advance through the single value displays using the Scroll button...
Manual 37218D easYgen-300 Series - Genset Control Default Operating Value Display The easYgen detects and selects the default operating value display by evaluating the measured voltage and the circuit breaker position. This default operating value is always displayed first. The operator may advance through...
Page 38
Manual 37218D easYgen-300 Series - Genset Control Parameter / display level Display Applies to Generator voltage easYgen-350X (phase-neutral) easYgen-350 easYgen-320X DL 2 easYgen-320 Generator voltage easYgen-350X Average of the phase voltages easYgen-350 (one of the three phase indica- easYgen-320X tors is displayed alternately)
Manual 37218D easYgen-300 Series - Genset Control Parameter / display level Display Applies to Engine speed easYgen-350X (display is not shown if the easYgen-350 MPU is disabled) easYgen-320X DL 1 easYgen-320 Operating hours counter easYgen-350X (display is six-digit with one...
J1939 Operating Value Display The easYgen-300 with the X package is able to display standard J1939 messages, which are sent by the engine control to the easYgen via the CAN bus. The values are displayed on the unit and in LeoPC1. In order to visual- ize J1939 messages with LeoPC1, the PC/laptop running LeoPC1 must be connected via the DPC interface (refer to page 32).
DL 1 65270 Table 7-3: J 1939 messages In case of a defective sensor or a broken wire the easYgen-300 displays four dashes instead of the J1939 value following the respective J1939 identifier. Figure 7-3: J1939 fault display The above display shows that the engine oil pressure (identifier 9r) sensor is defective or the cable from the sen- sor to the ECU is unplugged or broken.
J1939 DM1/DM2 Error Message Display The easYgen-300 with the X package is able to display J1939 DM1 and DM2 error messages, which are sent by the engine control to the easYgen via the CAN bus. The J1939 visualization can be configured with parame- ter 90, J1939 device type.
Manual 37218D easYgen-300 Series - Genset Control Alarm Messages If the easYgen detects a fault condition, LED starts to flash. The alarm message is displayed in the seven- segment display with a blinking "A" for alarm, an alarm number, and the respective alarm segment, if appli- cable.
Page 44
Manual 37218D easYgen-300 Series - Genset Control Alarm Alarm class Display Applies to 14 Mains rotation B: Alarm 350X field mismatch 320X 20 Engine overspeed F: Shutdown 350X 320X 21 Engine underspeed F: Shutdown 350X 320X 30 Start fail F: Shutdown...
Manual 37218D easYgen-300 Series - Genset Control Alarm Alarm class Display Applies to 65 J1939 DM1 amber Selectable 350X warning lamp B or F 320X 66 J1939 DM1 red Selectable 350X stop lamp B or F 320X Table 7-6: Alarm messages NOTE Discrete Inputs 4 &...
Page 46
Manual 37218D easYgen-300 Series - Genset Control Parameter Range Display Applies to Nominal speed 500 to 4000 rpm 350X [1 rpm interval] 320X Number of 2 to 260 teeth 350X teeth [1 tooth interval] 320X Cooldown time 0 to 999 s...
Page 47
Manual 37218D easYgen-300 Series - Genset Control Parameter Range Display Applies to Battery under- 8.0 to 42.0 V 350X voltage thre- [0.1 V interval] shold 320X Battery charge 0 = off, 1 = on 350X failure monitor- ing on/off 320X...
Manual 37218D easYgen-300 Series - Genset Control Parameter Range Display Applies to Mains phase 0 = Off 350X rotation moni- 1 = On toring - self 320X acknowledge J1939 Device 0 = Off 350X Type 1 = Standard 2 = Scania S6...
Manual 37218D easYgen-300 Series - Genset Control Application Modes ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The most important features of the application modes are illustrated in the following. Please note that the 2 breaker application mode is only possible with the easYgen versions [350], and [350X].
Manual 37218D easYgen-300 Series - Genset Control Operating Modes ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Operating Mode STOP NOTE Selecting the operating mode STOP is not the same as an EMERGENCY STOP. In some cases the ea- sYgen will perform additional logic functions, such as an engine cool down period, before the engine is stopped.
Manual 37218D easYgen-300 Series - Genset Control Operating Mode MANUAL NOTE You find an overview about the buttons, LEDs and the seven-segment display under Operation and Na- vigation on page 34. In the MANUAL operating mode (AUTO - MANUAL button...
Page 53
Manual 37218D easYgen-300 Series - Genset Control MCB close sequence: Action Breaker control Press the BREAKER CONTROL button Operation Open GCB The GCB close relay (relay 2) de-energizes to open the GCB – LED goes out Delay Breaker delay The control unit waits for the breaker transfer time configured in the...
Page 54
Manual 37218D easYgen-300 Series - Genset Control Engine start sequence: Action START Press the START - STOP button Delay Preglow time If diesel start logic is selected the relay will energize the glow plugs for the time configured in the engine parameters (page 73)
Page 55
Manual 37218D easYgen-300 Series - Genset Control Application Mode {1 breaker open/close} – [320], [320X], [350], [350X] The START - STOP button Starts the engine (if the engine is stopped, LED is not illuminated) Stops the engine (if the engine is running, LED...
Manual 37218D easYgen-300 Series - Genset Control Operating Mode AUTOMATIC In the AUTOMATIC operating mode, all engine, GCB, and/or MCB functions are operated via the discrete inputs or automatically by the control unit (i.e. a mains failure). The function of the easY- gen depends on the configuration of the unit and how the external signals are used.
Page 57
Manual 37218D easYgen-300 Series - Genset Control Detailed operation with 2 CBs in automatic mode (mains are not present) - [350], [350X] Preconditions: • Generator is stopped – LED is not illuminated • MCB is closed – LED is illuminated •...
Page 58
Manual 37218D easYgen-300 Series - Genset Control AMF / Auto Mains Failure Operation - [350], [350X] The operation sequence for an AMF operation is similar to the above sequence with the difference that a remote start signal is not required for the engine start and the engine monitoring delay time is not considered, i.e. the CBs are operated immediately.
Page 59
Manual 37218D easYgen-300 Series - Genset Control Detailed operation with 1 CB in Automatic mode Preconditions: • Generator is stopped – LED is not illuminated • Unit is in Automatic mode – LED is illuminated Start sequence: Action Remote start...
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Generator Circuit Breaker The easYgen-300 series has fixed breaker closure limits which prevent the GCB closure if the generator voltage and/or frequency is/are not within these limits. These limits depend on the parameters rated system frequency and rated generator voltage (refer to Measuring on page 71) and cannot be changed. The limits are set as follows:...
Series - Genset Control Functional Description of the Oil Pressure Input DI1 ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The easYgen-300 series is provided with an input for oil pressure. The function of this discrete input is described in the following. Vdc (GND) Discrete input DI1 (oil pressure)
Manual 37218D easYgen-300 Series - Genset Control Firing Speed Detection and Crank Termination ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The firing speed is used for crank termination if the parameter "Crank termination by DI1" is not enabled (refer to Parameter "Crank termination by DI1" on page 61 if this parameter is enabled). When "Crank termination by DI1"...
Functional Description of the Charging Alternator Input/Output ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The easYgen-300 series monitors the charging alternator operation with the following functionality. In some cases the alternator itself needs auxiliary excitation from an auxiliary DC source to build up its terminal voltage during start-up. For this, the battery will be connected into the alternator excitation windings during the engine start-up.
CB Close Delay Time ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The easYgen-300 series provides Delayed close GCB and Delayed close MCB (only [350], [350X]) signals in the list of configurable parameters (find more details about this under Relay Outputs on page 92) in order to meet the requirements of some special circuit breaker types which require an Enable CB Close signal before the actual CB close signal.
Functional Description of the Engine Released Signal ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The easYgen-300 series provides the engine released signal in the list of configurable parameters (find more de- tails about this under Relay Outputs on page 92). It is possible to use this signal for some special applications. Its functionality is described in the following for an emergency power supply.
Manual 37218D easYgen-300 Series - Genset Control Chapter 9. Configuration Restoring Default Values ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The easYgen can be reset to factory settings easily. This may be comfortable for configuring the easYgen from a known state. NOTE The unit has to be in Operating Mode STOP (page 51) to load the default values.
COM1 port of your notebook/PC. • You can now start the PC program as follows: - by "Start/Program/Woodward/LeoPC1" (version 3.1 or higher) and opening the respective cfg file, or - by a double click on the respective file ending ".cfg" in the subdirectory "/LeoPC1".
Configuring the Flags ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The easYgen-300 series provides four configurable LED flags in the alphanumerical display to indicate alarms. One or more alarm messages can be assigned to each one of these flags (i.e. the respective flag will be illumi- nated if the configured alarm state(s) occur(s) in addition to the regular alarm indication).
Manual 37218D easYgen-300 Series - Genset Control The flag parameters are displayed in LeoPC1 (refer to Configuration Using the PC on page 67 and the LeoPC1 user manual 37146 for more information) under System – Codes like shown in Figure 9-2 in default state (alarm "Start fail"...
Manual 37218D easYgen-300 Series - Genset Control Chapter 10. Parameters The following description of parameters is expanded to include all parameters that are accessible through LeoPC1. Not all parameters are accessible via the front panel. Most of the parameters, which are accessible via the front panel are password protected and are only accessible after entering a password.
Manual 37218D easYgen-300 Series - Genset Control Measuring ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Rated system frequency 50/60 Hz Rated system frequency Nennfrequenz im System The rated frequency of the system has to be configured here. [320] [320X] [350] [350X] The generator frequency monitoring as well as the mains failure limits refer to the value configured in this parameter.
Manual 37218D easYgen-300 Series - Genset Control Application ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Ignore CB reply YES/NO Ignore CB reply Ignoriere Rückmeldung LS This parameter controls the function of the discrete inputs DI4 and DI5. [320] [320X] [350] [350X] YES ..... The discrete inputs DI4 and DI5 are freely configurable. The pa- rameters of the discrete inputs can be accessed and configured via LeoPC1.
Manual 37218D easYgen-300 Series - Genset Control Engine ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Engine: Diesel Fuel relay close to stop / open to stop Fuel relay: close to stop Kraftstoffmagnet: Stopmag. close to stop . To stop the engine the stop solenoid is energized. Once speed is no...
Manual 37218D easYgen-300 Series - Genset Control Engine: Start/Stop Automatic Starter time 1 to 10 s Starter time Einrückzeit Anlasser The maximum time during which the crank relay remains enabled. The starter re- [320] [320X] [350] [350X] lay de-energizes when the engine reaches ignition speed or the configured time expires.
Manual 37218D easYgen-300 Series - Genset Control Breaker ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Transfer time GCB/MCB 0.10 to 99.99 s Transfer time GCBMCB Pasuenzeit GLSNLS Switching from generator supply to mains supply or from mains supply to gene- [320] [320X] [350] [350X] rator supply occurs automatically depending on the operating conditions. The time between the reply "power circuit breaker is open"...
Manual 37218D easYgen-300 Series - Genset Control Monitoring ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Time until horn reset 0 to 1,000 s Time until horn reset Zeit bis Hupenreset The alarm LED flashes and the centralized alarm (horn) is issued when a new B [320] [320X] [350] [350X] to F class alarm is detected.
Manual 37218D easYgen-300 Series - Genset Control Monitoring: Generator Underfrequency Generator underfrequency monitoring fixed to ON Monitoring Überwachung The generator underfrequency monitoring is always enabled and cannot be dis- [320] [320X] [350] [350X] abled. Generator underfrequency limit 50.0 to 130.0 %...
Manual 37218D easYgen-300 Series - Genset Control Monitoring: Generator Overvoltage Generator overvoltage monitoring fixed to ON Monitoring Überwachung The generator overvoltage monitoring is always enabled and cannot be disabled. [320] [320X] [350] [350X] Generator overvoltage limit 50.0 to 125.0 %...
Manual 37218D easYgen-300 Series - Genset Control Monitoring: Generator Undervoltage Generator undervoltage monitoring fixed to ON Monitoring Überwachung The generator undervoltage monitoring is always enabled and cannot be disabled. [320] [320X] [350] [350X] Generator undervoltage limit 50.0 to 125.0 %...
Manual 37218D easYgen-300 Series - Genset Control Monitoring: Mains Mains phase rotation monitoring ON / OFF Monitoring Überwachung ON ....Phase rotation monitoring is carried out according to the following [320] [320X] [350] [350X] parameters OFF ..... Monitoring is disabled.
Page 81
Manual 37218D easYgen-300 Series - Genset Control Emergency power: low voltage threshold 50.0 to 130.0 % Low voltage threshold Untere Grenzspannung This value refers to the Rated mains voltage (see page 71). [320] [320X] [350] [350X] This value is referred to for mains failure recognition and mains estimation. If the monitored value exceeds the adjusted limit, this is recognized as a mains failure and an emergency power operation is initiated.
Manual 37218D easYgen-300 Series - Genset Control Emergency power: frequency hysteresis 0.0 to 50.0 % Frequency hysteresis Frequenzhysterese This value refers to the Rated system frequency (see page 71). [320] [320X] [350] [350X] This value is referred to for mains failure recognition and mains estimation. If the monitored value exceeds the adjusted limit, this is recognized as a mains failure and an emergency power operation is initiated.
Manual 37218D easYgen-300 Series - Genset Control Monitoring: Engine Overspeed Engine overspeed monitoring ON / OFF Monitoring Überwachung ON ....Overspeed monitoring of the engine speed is carried out according [320] [320X] [350] [350X] to the following parameters. OFF ....No monitoring is carried out.
Manual 37218D easYgen-300 Series - Genset Control Monitoring: Engine Underspeed Engine underspeed monitoring fixed to ON Monitoring Überwachung The engine underspeed monitoring is always enabled and cannot be disabled. [320] [320X] [350] [350X] Engine underspeed limit fixed to 1,000 RPM...
Manual 37218D easYgen-300 Series - Genset Control Monitoring: Engine Start Fail Engine start fail monitoring fixed to ON Monitoring Überwachung The engine start fail monitoring is always enabled and cannot be disabled. [320] [320X] [350] [350X] Engine number of start attempts...
Manual 37218D easYgen-300 Series - Genset Control Monitoring: Battery Undervoltage Battery undervoltage monitoring fixed to ON Monitoring Überwachung The battery undervoltage monitoring is always enabled and cannot be disabled. [320] [320X] [350] [350X] Battery undervoltage limit 8.0 to 42.0 V...
Manual 37218D easYgen-300 Series - Genset Control Monitoring: Battery Charge Voltage Battery charge voltage monitoring ON / OFF Monitoring Überwachung ON ....Battery charge voltage monitoring is carried out according to the [320] [320X] [350] [350X] following parameters. OFF ....No monitoring is carried out.
It may be possible to configure all classes of alarms in this parameter but only alarm classes B and F are implemented in the easYgen-300 series. Ensure that only class B or F is con- figured here.
It may be possible to configure all classes of alarms in this parameter but only alarm classes B and F are implemented in the easYgen-300 series. Ensure that only class B or F is configured here.
It may be possible to configure all classes of alarms in this parameter but only alarm classes B and F are implemented in the easYgen-300 series. Ensure that only class B or F is configured here.
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The easYgen-300 series has 5 discrete inputs (DI1 to DI5). The discrete inputs 1 & 2 are pre-defined as alarm in- puts for oil pressure (DI1) and coolant temperature (DI2). The discrete input 3 is a control input for remote start.
Series - Genset Control Relay Outputs ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The easYgen-300 series has 6 (or 4 for [320] & [320X]) relay outputs. The relay outputs 3 and 4 can be freely configured with one signal output from the list of configurable parameters in Table 10-1 (only [350] &...
Manual 37218D easYgen-300 Series - Genset Control Configurable Parameter Description Applies to The assigned relay will energize if … [320] [320X] [350] [350X] Generator overfrequency 1 … the generator frequency is exceeded (refer to Monitoring: Generator Overfrequency on page 76 for details) Generator underfrequency 1 …...
Manual 37218D easYgen-300 Series - Genset Control Counter ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Maintenance hours 0 to 9,999 h Maintenance hours Wartungsintervall Stunden To disable the maintenance counter "hours" configure "0". [320] [320X] [350] [350X] This parameter defines the remaining hours until the next maintenance call oc- curs.
Manual 37218D easYgen-300 Series - Genset Control Interfaces ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ CAN Interface CAN baudrate 20/50/100/125/250/500/800/1000 kBd Baudrate Baudrate The CAN bus baudrate is configured here. [320] [320X] [350] [350X] NOTE The baud rate is the same for all devices connected to the CAN bus regardless of the selected protocol.
Manual 37218D easYgen-300 Series - Genset Control System ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Codes Set commissioning level code 0000 to 9999 Comissioning level code Code Inebtriebnahme Ebene The user may configure the HMI password (Parameter 00) here. The HMI pass- [320] [320X] [350] [350X] word protects the configuration of the unit via the front panel.
Series - Genset Control Flags The easYgen-300 series provides four configurable LED flags in the alphanumerical display to indicate alarms. One or more alarm messages can be assigned to each one of these flags (i.e. the respective flag will be illumi- nated if the configured alarm state(s) occur(s) in addition to the regular alarm indication).
Manual 37218D easYgen-300 Series - Genset Control Versions NOTE The following parameters are not configurable. They may be viewed using LeoPC1 for information pur- poses only. Serial number (S/N) display only Serial number Seriennummer This is the serial number of the easYgen and identifies the control clearly.
The event logger is a FIFO (First In/First Out) memory for logging alarm events and operation states of the unit. The capacity of the event logger is 15 entries. Additional event messages overwrite the oldest messages. Since the easYgen-300 units do not include a clock module, the operating hours are stored with each event logger entry as the timestamp.
Manual 37218D easYgen-300 Series - Genset Control Reading Out GetEventLog On the Eventlog tab of GetEventLog, click the Request Eventlog button to read out the content of the event log- ger memory. The content of the event logger is displayed as shown in Figure 11-2.
Manual 37218D easYgen-300 Series - Genset Control Chapter 12. Technical Data Name plate ------------------------------------------------------------------------------------------------------ Serial number (numerical) Serial number (Barcode) Date of production (YYMM) Item number Item revision number Details Technical data Type Unit name Type Extended description UL sign (Example for a typical name plate) Measuring values ------------------------------------------------------------------------------------------ /Δ...
Page 102
Manual 37218D easYgen-300 Series - Genset Control MPU Input ------------------------------------------------------------------------------- capacitive isolated Input impedance ..................min. approx. 17 kΩ Input voltage ...................... 875 mV eff. Pre-exciter current output D+ ------------------------------------------------------------------------------ Max. exciter current 12 Vdc (terminal 4)........... 0.11 Adc 24 Vdc (terminal 3)........... 0.11 Adc...
Manual 37218D easYgen-300 Series - Genset Control Chapter 13. Accuracy Measuring value Display Accuracy Notes Frequency Generator 15.0 to 85.0 Hz 0.1 % Mains 40.0 to 85.0 Hz 0.1 % Voltage Generator 0 to 600 V Transformer ratio selectable Mains...
Manual 37218D easYgen-300 Series - Genset Control Appendix A. Common Alarm Classes ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The easYgen-300 series provides only the alarm classes B & F: Alarm class Visible in the display LED "Alarm" Relay "Close GCB" Shut-down engine Engine blocked until &...
Manual 37218D easYgen-300 Series - Genset Control Conversion Factors and Charts ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Conversion Factors: Temperature °C °F °F °C ° − ° Value ° ° ° × ° ° ° Value ° ° Table 13-1: Conversion factor: temperature Conversion Factors: Pressure Value ×...
Manual 37218D easYgen-300 Series - Genset Control Appendix B. J1939 Protocol Descriptions Visualizing J1939 Measuring Values with LeoPC1 ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ These J1939 measuring values are received by the easYgen via CAN bus from the ECU and visualized in LeoPC1 using direct configuration. The PC/laptop running LeoPC1 must be connected to the easYgen via the DPC interface (refer to page 32).
Manual 37218D easYgen-300 Series - Genset Control Special EMR Messages Type Message acc. to EMR manual Display in LeoPC1 Engine stop information no stop Engine safety Type 1. Engine safety CAN message engine stop request Type 2: CAN message engine stop request...
Series - Genset Control Appendix C. Front Customization The easYgen-300 series is designed language-independent, but can be customized to your demands using paper strips. The left paper strip is intended for customization and may contain more detailed information about the display.
Appendix D. Troubleshooting If problems are encountered while commissioning or operating the easYgen-300, please refer to the troubleshoot- ing table below and LeoPC1 prior to contacting Woodward for technical assistance. The most common problems and their solutions are described in the troubleshooting table. If problems are encountered between the easYgen- 300 and its wiring and the engine or other devices, refer to the respective manuals for solving the problem.
Page 110
Manual 37218D easYgen-300 Series - Genset Control Symptom Possible cause Possible solution Verify "Generator Circuit Breaker "Generator Circuit Breaker Measure the voltage between ter- If the circuit breaker is closed, Closed" LED is not lit, al- Closed" signal is miswired.
Page 111
Manual 37218D easYgen-300 Series - Genset Control Symptom Possible cause Possible solution Verify Alarm "30A - Start fail" oc- Low fuel situation. Check, if enough Fuel is present to Fuel level is above fuel pick- curs. run the engine. up and fuel system is properly...
Page 112
Manual 37218D easYgen-300 Series - Genset Control Symptom Possible cause Possible solution Verify Alarm "21A - Underspeed" Pickup Sensor is miswired to the Check whether the pickup sensor is The easYgen-300 requires 2 occurs, after engine has fired. easYgen-300. properly wired to terminals 37...
Page 113
Manual 37218D easYgen-300 Series - Genset Control Symptom Possible cause Possible solution Verify CAN / J1939 Communication The parameter for enabling the Check for setting of Parameter 90 Parameter 90 "J1939 Device does not work. J1939 Communication is confi- "J1939 Device Type" in the confi- Type"...
Manual 37218D easYgen-300 Series - Genset Control Appendix E. List of Parameters Unit number P/N _____________________________ Rev _______________________________ Version easYgen- ______________________________________________________________ Project ______________________________________________________________________ Serial number S/N _______________ Date ______________________________ Parameter Setting range Default value Customer setting PASSWORD HMI Password 0000 to 9999...
Page 115
Manual 37218D easYgen-300 Series - Genset Control Parameter Setting range Default value Customer setting EMERGENCY POWER (AMF) [350] On/Off ON/OFF [350X] [350] Mains fail delay time 0.20 to 99.99 s 3.00 s [350X] [350] Mains settling time 0 to 9,999 s...
Page 116
Manual 37218D easYgen-300 Series - Genset Control Parameter Setting range Default value Customer setting MONITORING Engine: Overspeed Monitoring ON/OFF [3x0X] Limit 0 to 9,999 RPM 1,850 RPM [3x0X] [3x0X] Delay 0.1 s 0.1 s Alarm class [3x0X] [3x0X] Self acknowledge...
Page 117
Manual 37218D easYgen-300 Series - Genset Control Parameter Setting range Default value Customer setting DISCRETE INPUTS Discrete input [DI1] oil pressure DI 1 operation N.O. N.O. DI 1 delay 0.5 s 0.5 s DI 1 alarm class DI 1 delayed by eng. speed...
Page 118
Manual 37218D easYgen-300 Series - Genset Control Parameter Setting range Default value Customer setting SYSTEM Codes Comissioning level code 0000 to 9999 0003 Factory settings ON / OFF Clear event log ON / OFF Set default values ON / OFF...
Page 119
Manual 37218D easYgen-300 Series - Genset Control Parameter Setting range Default value Customer setting SYSTEM Flag 3 gen. overfreq. 1 YES/NO Flag 3 gen. underfreq. 1 YES/NO Flag 3 gen. overvolt. 1 YES/NO Flag 3 gen. undervolt. 1 YES/NO Flag 3 mains rot. field alarm...
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ If a control (or any part of an electronic control) is to be returned to Woodward for repair, please contact Wood- ward in advance to obtain a Return Authorization Number. When shipping the unit(s), attach a tag with the fol- lowing information: •...
Stuttgart [+49 (0) 711 789 54-0]. They will help expedite the processing of your order through our distributors or local service facility. To expedite the repair process, contact Woodward in advance to obtain a Return Authoriza- tion Number, and arrange for issue of a purchase order for the unit(s) to be repaired. No work can be started until a purchase order is received.
+49 (0) 711 789 54-100 email: stgt-info@woodward.com For assistance outside Germany, call one of the following international Woodward facilities to obtain the address and phone number of the facility nearest your location where you will be able to get information and service. Facility...
Series - Genset Control Engineering Services ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Woodward Industrial Controls Engineering Services offers the following after-sales support for Woodward products. For these services, you can contact us by telephone, by e-mail, or through the Woodward website. • Technical support •...
Manual 37218D easYgen-300 Series - Genset Control Technical Assistance ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ If you need to telephone for technical assistance, you will need to provide the following information. Please write it down here before phoning: Contact Your company ____________________________________________________ Your name _______________________________________________________...
Page 125
Phone +49 (0) 711 789 54-0 • Fax +49 (0) 711 789 54-100 stgt-info@woodward.com Homepage http://www.woodward.com/power Woodward has company-owned plants, subsidiaries, and branches, as well as authorized distributors and other authorized service and sales facilities throughout the world. Complete address/phone/fax/e-mail information for all locations is available on our website (www.woodward.com).
Need help?
Do you have a question about the easYgen-300 and is the answer not in the manual?
Questions and answers