Output Circuit Configuration - Mitsubishi Electric MELSEC FX2NC-16MT-D/UL Hardware Manual

Fx2nc series programmable controllers
Table of Contents

Advertisement

FX2NC Series Programmable Controllers
6.2.2

Output circuit configuration

An internal protection circuit for the relays is not provided in the relay output circuit for this
product. It is recommended to use inductive loads with built-in protection circuits. When using
loads without built-in protection circuits, insert an external contact protection circuit, etc. to
reduce noise and extend the product life.
1) DC load
Connect a diode in parallel with the load.
The diode (for commutation) must comply with the
following specifications.
Item
Reverse voltage
Forward current
2) AC load
Connect the surge absorber shown to the right
(combined CR components such as a surge killer
and spark killer, etc.) parallel to the load.
Select the rated voltage of the surge absorber
suitable to the output used. Refer to the table below
for other specifications.
Electrostatic capacitance
Resistance value
Guide
5 to 10 times the load voltage
Load current or more
Item
Approx. 0.1
Approx. 100 to 200
PLC output
contact
PLC output
contact
Guide
µ
F
Outputs 6.
Inductive load
Diode
(for commutation)
Inductive load
Surge
absorber
6-9