COMMISSIONING AND ADDITIONAL INSTRUCTIONS
WARNING!
Do not touch the internal components or the circuit boards of the drive when the
drive is connected to mains. These components are live. A contact with this voltage
is very dangerous.
WARNING!
Do not make connections to or from the AC drive when it is connected to mains.
There is a dangerous voltage.
WARNING!
To do work on the connections of the drive, disconnect the drive from mains. Wait 5
minutes before you open the cabinet door or the cover of the drive. Then use a
measuring device to make sure that there is no voltage. The connections of the
drive are live 5 minutes after it is disconnected from mains.
WARNING!
Before you do electrical work, make sure that there is no voltage.
DOWNLOADING WITH MAINS, MR8-MR12
When the drive is supplied from mains, you can download a new software with the Vacon
Loader PC tool and a CAB-USB/RS485 cable.
1
To download a new software, connect the PC into
the control panel connector with the CAB-USB/
RS485 cable.
The downloading time:
MR8 and MR9: approximately 6 minutes
MR10: approximately 12 minutes
MR12: approximately 25 minutes
When the drive is not supplied from mains, there are 2 alternatives to download the
software.
1. The first is to use the Software Service Kit. The kit enables the power-up of the control
board without the power-up of the drive, and enables you to download the software.
Refer to the Software Service Kit User Manual for more information. In MR10 and MR12,
you must also connect an external 24 VDC into the connector X50 on the measurement
board.
2. The second alternative is to use an external 24 VDC power supply. Refer to the
instructions below.
DOWNLOADING WITHOUT MAINS, MR8-MR12
When the drive is not supplied from mains, use an external 24 VDC power supply to do
power-up to the control unit. In MR8 and MR9, the external 24 VDC does power up to the
control unit, and in MR10 and MR12, it does power up to the control unit and the
measurement board(s). After the power-up you can download the software.