SMC Networks EX250 series Operation Manual

For cc-link
Hide thumbs Also See for EX250 series:

Advertisement

Quick Links

Fieldbus device
Operation Manual
EX250 Series for CC-Link
Thank you for purchasing an SMC EX250 Series Fieldbus device (Hereinafter
referred to as "SI unit" ).
Please read this manual carefully before operating the product and make sure you
understand its capabilities and limitations.
Please keep this manual handy for future reference.
To obtain more detailed information about operating this product,
please refer to the SMC website (URL http://www.smcworld.com) or
contact SMC directly.
Safety Instructions
These safety instructions are intended to prevent hazardous situations and/or
equipment damage.
These instructions indicate the level of potential hazard with the labels of
"Caution", " Warning" or "Danger". They are all important notes for safety and
must be followed in addition to International standards (ISO/IEC) and other safety
regulations.
Caution:
CAUTION indicates a hazard with a low level of risk which, if
not avoided, could result in minor or moderate injury.
WARNING indicates a hazard with a medium level of risk
Warning:
which, if not avoided, could result in death or serious injury.
DANGER indicates a hazard with a high level of risk which, if
Danger:
not avoided, will result in death or serious injury.
Operator
This operation manual is intended for those who have knowledge of machinery
using pneumatic equipment, and have sufficient knowledge of assembly,
operation and maintenace of such equipment. Only those persons are allowed
to perform assembly, operation and maintenance.
Read and understand this operation manual carefully before assembling,
operating or providing maintenance to the product.
Safety Instructions
Warning
Do not disassemble, modify (including changing the printed circuit board) or repair.
An injury or failure can result.
Do not operate the product outside of the specifications.
Do not use for flammable or harmful fluids.
Fire, malfunction, or damage to the product can result.
Verify the specifications before use.
Do not operate in an atmosphere containing flammable or explosive gases.
Fire or an explosion can result.
This product is not designed to be explosion proof.
If using the product in an interlocking circuit:
•Provide a double interlocking system, for example a mechanical system.
•Check the product regularly for proper operation.
Otherwise malfunction can result, causing an accident.
The following instructions must be followed during maintenance:
•Turn off the power supply.
•Stop the air supply, exhaust the residual pressure and verify that the air is released before performing
maintenance.
Otherwise an injury can result.
Caution
After maintenance is complete, perform appropriate functional inspections.
Stop operation if the equipment does not function properly.
Safety cannot be assured in the case of unexpected malfunction.
Provide grounding to assure the safety and noise resistance of the Fieldbus system.
Individual grounding should be provided close to the product with a short cable.
NOTE
When conformity to UL is necessary the SI unit must be used with a UL1310
Class2 power supply.
Summary of Product element
6
5
1
4
3
Tie-rod(2 pcs)
2
accessory
3
No.
Description
Function
1
Communication connector
Connect with CC-Link communication line. (Accessory)
Supplies power to the solenoid valve, the Output block, SI unit and
2
Power supply connector
the Input block.
3
Input block connector
Connects the Input block.
4
Output block connector
Connects the solenoid valve, Output block and etc.
5
Display
LED display shows the SI unit status.
6
Switch protective cover
Set Station no. and Baud rate by using the switches under the cover.
7
Ground terminal (FE)
Used for grounding.
Mounting and Installation
Installation
Not having mounting hole, it can't be set to BUS independently. Be sure to connect
manifold to SI unit for setting.
And if Input block is unnecessary, connect End plate directly to SI unit.
Assembly and disconnection of unit
M3 hexagon screw
Tie rod
Tightening torque: 0.6 Nm
Tightening torque: 0.6 Nm
R
3
X
12
PWR
P
1
A
End plate
SI unit
Valve manifold
Exchange of SI unit
•Remove screws from End Plate and release connection of each unit.
•Replace old SI unit with new one. (Tie rod does not need to be removed.)
•Connect Input Block and End Plate and tighten removed screws by specified
tightening torque. (0.6 Nm)
Assembly and disconnection of unit
Addition of Input Block
•Remove screws from End Plate.
•Mount attached tie rod.
•Connect additional Input Block.
•Connect End Plate and tighten removed screws by specified tightening torque.
(0.6 Nm)
Caution for maintenance
(1) Be sure to turn-off all power supplies.
(2) Be sure that there is no foreign object in any of units.
(3) Be sure that gasket is lined properly.
(4) Be sure that tightening torque is according to specification.
If these items are not kept, it may lead to the breakage of substrate or intrusion of
liquid or dust into the units.
Wiring
Communication wiring
•Communication connector (Bus adapter: EX9-ACY00-MJ)
LINK OUT
LINK IN
LINK IN: M12 4pins plug A-coded
Pin No.
Description
Function
2
2
1
SLD
Shield
1
5
1
3
3
2
DB
Communication wire DB
4
4
3
DG
Communication wire DG
4
DA
Communication wire DA
Example of the cable with connector: PCA-1567720 (SMC)
Example of the connector:
PCA-1557620 (SMC)
LINK OUT: M12 5pins socket A-coded
Pin No.
Description
Function
1
SLD
Shield
2
DB
Communication wire DB
3
DG
Communication wire DG
4
DA
Communication wire DA
5
-
Unused
Example of the cable with connector: PCA-1567717 (SMC)
Example of the connector:
PCA-1557617 (SMC)
•Power supply connector
M12 5pins plug B-coded (reverse)
Pin No.
3
2
1
5
2
4
1
3
4
5
Example of the cable with connector: EX9-AC010-1 (1 m)
Power for sensor is supplied to sensor connected with Input block. Select sensor
concerning voltage drop up to maximum 1 V inside the unit at this moment.
If sensor requires 24 V, it is necessary to lower power supply voltage for sensor
slightly or secure power supply for sensor separately without going through SI unit so
that sensor input voltage can be 24 V with actual loading (allowable voltage of power
supply: 19.2 V to 28.8 V).
Voltage drop of max.1 V
SW power
24 VDC
SI unit
Terminator
Station No. and Baud rate are set by the rotary switch inside of the SI unit cover.
Set parameters while the power of SI unit is OFF.
The setting of each switches can be fixed after power is ON.
Terminating resistance and cable
If this SI unit is the terminal of CC-Link connection, connect the terminal resistor to
"OUT" side of the bus adapter. There are two types of terminal resistors depending on
the cable to use.
Refer to the following table and select an appropriate terminal resister.
Ver. 1.10-compatible CC-Link dedicated cable
Cable to use
CC-Link dedicated (110 Ω,1/2 W)
Manufacturer
Model
Color of molded portion
Correns
VA-4DCC-110
Black
R
PHOENIX
SAC-4P-M12MS
Black
3
CONTACT
CCL TR
X
B
B
12
P
Setting
A
1
Switch setting
Station No., Baud rate and HOLD/CLEAR are set by the switch inside of the SI unit
cover.
Set parameters while the power of SI unit is OFF.
The setting of each switches can be fixed after power is ON.
•Station no. setting
Setting
STATION No.
x10
x1
0
0
9
1
9
1
8
2
8
2
: Set stations within 01 to 63
7
3
7
3
"L ERR" display lights if 00 and station 64 or larger is selected.
6
4
6
4
5
5
Turn off the power and select correct station.
×10
×1
: "L ERR" display blinks if the switch is operated which the
power is ON.
•Baud rate setting
Setting
0
1
9
1
8
2
2
7
3
3
6
4
5
4
5
: Set stations within 01 to 63
"L ERR" display lights if 00 and station 64 or larger is selected.
Turn off the power and select correct station.
: "L ERR" display blinks if the switch is operated which the
power is ON.
•HOLD/CLEAR setting
Setting
Contents
H
H (ON)
HOLD
C
C (OFF)
CLEAR
Adjusted when shipped
Please refer to the table below for setting at the time of shipment from the factory.
Set parameters
Switch setting
B RATE (Baud rate)
0
x10
0
STATION NO.
x1
0
HOLD/CLEAR
C(OFF)
Assignment of I/O number
•Standard wiring
The outputs of the SI unit are assigned from the D side solenoid valve in the order
Description
Function
0,1,2...maximum of 31.
SV24 V
+24 V for solenoid valve.
Refer to each solenoid valves catalogue for details.
SV0 V
0 V for solenoid valve
The inputs of the Input block are assigned from the SI unit side Input block in the
order 0,1,2...maximum of 31.
SW24 V
+24 V for SI unit and Input Block
SW0 V
0 V for SI unit and Input Block
•Semi‐standard wiring for valve output (Mixed wiring)
FE
Ground
As semi-standard wiring, mixed wiring inside the manifold is available. The wiring
type is specified by description of single or double solenoid valve mounted on the
manifold .In order to specify the mixed wiring, completion of Manifold type solenoid
EX9-AC030-1 (3 m)
valve Specifications Sheet is required.
EX9-AC050-1 (5 m) etc. (SMC)
LED indication
LED
Sensor
23 VDC
Rotary switch for baud
rate setting
Input block
LED
PW
PW (V)
L RUN
L ERR
"PW", "PW(V)", "L RUN" light while data link is normal.
CC-Link dedicated high-performance cable
(130 Ω,1/2 W)
Model
Color of molded portion
VA-4DCC-130
Grey
Troubleshooting
Technical documentation giving detailed troubleshooting information can be found
on the SMC website (URL http://www.smcworld.com).
Specifications
Setting range
0 to 6
0 to 9
Power for SI unit/Input Block: 24 VDC ±20%, 1.1 A or less
Power for solenoid valve: 24 VDC +10%/5%, 2 A or less
Connection load: Solenoid valve with protection circuit for 24 VDC and 1.5 W or less surge
voltage. (made by SMC)
Setting range
Operating ambient temp: 5 to 45
156 kbps
Pollution degree: Pollution degree 3 (UL508)
625 kbps
Technical documentation giving detailed specification information can be found on
2.5 Mbps
the SMC website (URL http://www.smcworld.com).
5 Mbps
10 Mbps
Outline Dimensions
Technical documentation giving detailed outline dimensions information can be
found on the SMC website (URL http://www.smcworld.com).
Accessories
Function
Hold the last state before communication error.
Technical documentation giving detailed accessories information can be found on
Clear all outputs.
the SMC website (URL http://www.smcworld.com).
Contents
156 kbps
0
CLEAR
URL http://www.smcworld.com
Akihabara UDX 15F, 4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021, JAPAN
Phone: +81 3-5207-8249 Fax: +81 3-5298-5362
Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer.
© 2011 SMC Corporation All Rights Reserved
PW(V)
PW
Rotary switch for
station no. setting
B RATE
STATION NO
×10
×1
L RUN
L ERR
Contents
Lights up: Input and control power is ON.
Lights off: Input and control power is OFF.
Lights up: When power supply for solenoid valves is turned ON.
Lights off: When supply voltage decreases below 19 V.
Lights up: Communication is normal.
Lights off: Communication terminated. (Time over error)
Lights up: Communication error.
Flashing: Assignment of station no. and baud rate are made
during communication. (Flicker every 0.4 s)
Lights off: Communication is normal.
(
)
Inside of SI unit: 0.1 A or less
Input block: 1 A or less
(
Depending on number of connecting
sensors and specifications)
(Depending on number of solenoid valve station and
specifications)
o
C
Storage ambient temp: -20 to 60
o
C