Assumptions; Diagnostics - ABB TTH200 Additional Instructions

Temperature transmitter; additional instructions for iec 61508 compliant devices
Hide thumbs Also See for TTH200:
Table of Contents

Advertisement

TTH200, TTR200, TTF200 TEMPERATURE TRANSMITTER | SM/TTX200/SIL-EN REV. E

Assumptions

The following assumptions have been made during the Failure Modes, Effects, and Diagnostic Analysis:
Failure rates are constant, wear out mechanisms are not included.
Propagation of failures is not relevant.
The HART protocol is only used for setup and diagnostics purposes, not during normal operation.
The device is installed per manufacturer's instructions.
Failures during parameterization are not considered.
The correct parameterization is checked be the end user.
Sufficient tests are performed prior to shipment to verify the absence of vendor and / or manufacturing defects that prevent
proper operation of specified functionality to product specifications or cause operation different from the design analyzed.
External power supply failure rates are not included.
As the optional display / control unit can interfere with the transmitter, the contribution to the dangerous undetected failure
rate was considered.
The worst case internal fault detection time is 2 minutes.
Only the current output 4 to 20 mA is used for safety applications.
Only one input and one output are part of the considered safety function.
The application program in the safety logic solver is configured according to NAMUR NE43 to detect under-range low alarm
and over-range high alarm and does not automatically trip on these states; therefore, these failures have been classified as
dangerous detected failures.
Materials are compatible with process conditions.
The measurement / application limits are considered.
Short circuit and lead breakage detection are activated.
The minimum supply voltage used for the failure rate calculation is 15 VDC.

Diagnostics

The device's diagnostics setup meets the declared safety requirements in supporting the following runtime error detections:
Sensor configuration RTD: wire break and short circuit
Sensor configuration thermocouple: wire break
Several electrical part failures
AD-converter error
Internal Power Supply error
Internal communication error
Program and Microcontroller supervision through watchdog
Sensor limit range alarm (upper and lower limits)
Flash ROM CRC16 error
EEPROM CRC16 error
RAM Physical – Pattern Test error
RAM CRC16 data error