ABB RED650 Applications Manual page 60

Relion 650 series, line differential protection version 2.2
Hide thumbs Also See for RED650:
Table of Contents

Advertisement

Section 4
Analog inputs
54
For correct terminal designations, see the connection diagrams
valid for the delivered IED.
Protected Object
L1
L2
L3
INS
a)
b)
INS
IEC11000029 V4 EN-US
Figure 15:
Connections for single-phase CT input
Where:
1)
shows how to connect single-phase CT input in the IED.
2)
is TRM where these current inputs are located. It shall be noted that for all these
current inputs the following setting values shall be entered.
For connection (a) shown in Fgure 15:
CTprim = 1000 A
CTsec = 1A
CTStarPoint = ToObject
For connection (b) shown in Figure 15:
CTprim = 1000 A
CTsec = 1A
CTStarPoint = FromObject
3)
shows the connection made in SMT tool, which connect this CT input to the fourth input
channel of the preprocessing function block 4).
4)
is a Preprocessing block that has the task to digitally filter the connected analog inputs
and calculate values. The calculated values are then available for all built-in protection
and control functions within the IED, which are connected to this preprocessing
function block.
If frequency tracking and compensation is required (this feature is typically required
only for IEDs installed in the power plants) then the setting parameters
shall be set accordingly.
IED
2
1
(+)
(+)
(-)
(+)
(-)
(-)
Line differential protection RED650 2.2 IEC
1MRK 505 393-UEN B
4
SMAI2
BLOCK
AI3P
REVROT
AI1
^GRP2L1
AI2
^GRP2L2
AI3
^GRP2L3
AI4
^GRP2N
AIN
3
IEC11000029-4-en.vsdx
DFTReference
Application manual