Internal/External Fault Discriminator - ABB RED650 Applications Manual

Relion 650 series, line differential protection version 2.2
Hide thumbs Also See for RED650:
Table of Contents

Advertisement

Section 6
Differential protection
6.1.3.4
92
nd
CT saturation causes 2
side, which contributes to the stabilization of the relay at through fault conditions.
It is strongly recommended to maintain a sensitive setting of the I2/I1Ratio also
when a power transformer is not included in the protected zone.
I5/I1Ratio
The set value is the ratio of the 5
fundamental frequency of the differential current. To obtain this information, the
instantaneous differential current must be analyzed.
A 20...30% over-excitation of a transformer can cause an increase in the excitation
current of 10...100 times the normal value. This excitation current is a true
differential current if the transformer is inside the protected zone. It has a high
th
degree of the 5
harmonic, and the default setting of 25% will be suitable in most
cases to detect the phenomenon. As CT saturation also causes 5
secondary side, it is recommended to maintain this setting at 25% or lower even if
no power transformer is included in the protected zone.

Internal/external fault discriminator

NegSeqDiffEn
The negative sequence fault discriminator can be set On/Off. It is an important
complement to the percentage restrained differential function. As it is directional, it
can distinguish between external and internal faults also in difficult conditions,
such as CT saturation, and so on. It is strongly recommended that it is always
activated (On).
NegSeqROA
This is the setting of the relay operate angle of the negative sequence current based
internal/external fault discriminator. The directional test is made so that the end
with the highest negative sequence current is found. Then, the sum of the negative
sequence currents at all other circuit ends is calculated. Finally, the relative phase
angle between these two negative sequence currents is determined. See figure 40.
Ideally the angle is zero degrees for internal faults and 180 degrees for external
faults. However, measuring errors caused by, for example, CT saturation as well as
different phase angles of the negative sequence impedances, require a safety
margin, expressed as the ROA (Relay Operate Angle). The default value 60
degrees is recommended in most cases. The setting NegSeqROA is a compromise
between the security and dependability of the differential protection. The value
NegSeqROA = 60 degrees emphasizes security against dependability. Tests have
proven that 60 degrees is a good choice.
harmonics of considerable value on the CT secondary
th
harmonic of the differential current to the
1MRK 505 393-UEN B
th
harmonics on the
Line differential protection RED650 2.2 IEC
Application manual
M12541-206 v4
M12541-210 v2
M12541-213 v4
M12541-218 v4

Advertisement

Table of Contents
loading

Table of Contents