ABB RED650 Applications Manual page 100

Relion 650 series, line differential protection version 2.2
Hide thumbs Also See for RED650:
Table of Contents

Advertisement

Section 6
Differential protection
94
IED
IEC05000442 V2 EN-US
Figure 41:
One two–winding transformer in the protected zone
IED
IEC04000209 V2 EN-US
Figure 42:
One two–winding transformer in the protected zone
Another alternative is with one three-winding transformer in the protected zone,
shown in Figure 43. Observe that in this case, the three-winding power transformer
is seen by the differential protection as two separate power transformers, A and B,
which have one common winding on the HV side.
A
IED
IEC15000451 V2 EN-US
Figure 43:
One three–winding transformer in the protected zone
TraAOnInpCh
This parameter is used to indicate that a power transformer is included in the
protection zone at current terminal X. This can be either a two-winding transformer
Protected zone
Protected zone
IED
Protected zone
T
T
Line differential protection RED650 2.2 IEC
1MRK 505 393-UEN B
IED
IEC05000442-2-en.vsdx
IED
IEC04000209-2-en.vsdx
B
IED
IEC15000451-2-en.vsdx