Current Reversal And Weak-End Infeed Logic For Distance Protection 3-Phase Zcrwpsch; Identification; Application; Current Reversal Logic - ABB RED650 Applications Manual

Relion 650 series, line differential protection version 2.2
Hide thumbs Also See for RED650:
Table of Contents

Advertisement

1MRK 505 393-UEN B
13.2
13.2.1
13.2.2
13.2.2.1
Line differential protection RED650 2.2 IEC
Application manual
tSendMin
Set
= 0.1 s (0 s in parallel line applications)
Set
Unblock
=
tSecurity
Set
= 0.015 s
Current reversal and Weak-end infeed logic for
distance protection 3-phase ZCRWPSCH

Identification

Function description
Current reversal and weak-end infeed
logic for distance protection 3-phase

Application

Current reversal logic

To avoid this kind of disturbances, a fault current reversal logic (transient blocking
logic) can be used.
The unwanted operations that might occur can be explained by looking into
Figure
122
and Figure 123. Initially the protection A2 at A side will detect a fault
in forward direction and send a communication signal to the protection B2 at
remote end, which is measuring a fault in reverse direction.
L1
A1
L2
A2
IEC99000043 V3 EN-US
Figure 122:
Current distribution for a fault close to B side when all breakers are
closed
When the breaker B1 opens for clearing the fault, the fault current through B2 bay
will invert. If the communication signal has not reset at the same time as the
distance protection function used in the teleprotection scheme has switched on to
forward direction, we will have an unwanted operation of breaker B2 at B side.
Off
IEC 61850
identification
ZCRWPSCH
B1
B2
IEC9900043-2.vsd
Section 13
Scheme communication
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
85
IP15751-1 v4
M15073-1 v5
IP15023-1 v1
M13895-4 v6
285

Advertisement

Table of Contents
loading

Table of Contents