Setup Steps - Vega VEGAPULS 61 Quick Setup Manual

Radar sensor for continuous level measurement of liquids, profibus pa
Hide thumbs Also See for VEGAPULS 61:
Table of Contents

Advertisement

Set parameters
Parameterization example
VEGAPULS 61 • Profibus PA
5 Set up with the display and adjustment module PLICSCOM
5.2

Setup steps

1. Go to the menu "Basic adjustment" via the display and adjust-
ment module.
Basic adjustment
Display
Diagnostics
Service
Info
2. Carry out the adjustment in the menu items "Min. adjustment" and
"Max. adjustment".
Max. adjustment
100.00 %
=
1.000 m(d)
2.000 m(d)
Min. adjustment
0.00 %
=
5.000 m(d)
4.000 m(d)
3. Select in the menu item "Medium" the medium of your applica-
tion, for example "Aqueous solution".
Medium
Liquid
4. Select in the menu item "Application" the vessel, the application
and the vessel form, for example, "Storage tank".
Vessel form
Storage tank
The radar sensor measures the distance from the sensor to the prod-
uct surface. For indication of the real filling height, an allocation of the
measured distance to the percentage height must be carried out.
The actual level is then calculated on the basis of these entered
values. At the same time, the operating range of the sensor is limited
from maximum range to the requested range.
11