I/O Wiring
DI dry contact mode
DI wet contact mode (Ch-Ch isolation)
DI wet contact PNP/NPN mode (No CH-CH isolation)
– 4 –
DIO_DI wet contact mode (no CH-CH isolation)
DIO_DO sink mode

System Configuration

Configuration via Web Console
Configuration of an ioLogik E1500 is done via the web console.
Default IP Address: 192.168.127.254
Subnet Mask: 255.255.255.0
Note: Be sure to configure the host PC's IP address to the same
subnet as the ioLogik E1500. For example, 192.168.127.253.
ioSearch Utility
ioSearch is a search utility that helps users locate an ioLogik E1500
on the local network. The utility can be found in the Documentation
and Software CD under Software  ioSearch; the latest version
can be downloaded from Moxa's website.
– 5 –
Load Factory Default Settings
There are three ways to restore the ioLogik E1500 to the factory
default settings.
1. Remove the two screws and the aluminum plate, and then
press and hold the RESET button for 5 seconds.
2. Right click the specified ioLogik in the ioSearch utility and
select Reset to Default.
3. Select Load Factory Default from the web console.
Modbus Address Table
Refer to the user's manual for details of the ioLogik's Modbus
address, or refer to the start address of the I/O channels in the
web console under User-defined Modbus Addressing  Default
Address.
Active OPC Server Connection
Take the following steps to connect the ioLogik E1500 to an Active
OPC Server:
1. Disable the user-defined Modbus address function.
2. Install the Active OPC Server Lite Package from the
Documention and Software CD under Software  AOPC Lite 
ActiveOPCSetup  Install.exe.
3. Install from the Web console under Active OPC Server Settings
 AOPC & I/O Settings. and specify the IP address of the
Active OPC Server. Specify the I/O channels that need to be
added to Active OPC Server Lite, submit the settings, and then
click Save/Restart.
4. From the web console under Active OPC Server Settings 
Create AOPC Tag, click the "Create Tag" button.
5. Launch Active OPC Server Lite from Start  Programs  MOXA
 IOServer  ActiveOPC  ActiveOPC. Save the configuration
before exiting the Active OPC Server Lite program.