Environmental Data; Response Times - Invertek Drives eco OPTIDRIVE Advanced User's Manual

Ac variable speed drive 0.75kw – 250kw / 1hp – 350hp, 200 – 480 volt 1 & 3 phase
Table of Contents

Advertisement

4.3. Environmental Data

4.3.1.
Temperature Range
Ambient Temperature Range : Operation
Note : No frost or condensation permissible
Ambient Temperature Range : Storage
4.3.2.
Altitude
Maximum Altitude (No derating)
Maximum Altitude (UL Approved)
Maximum Altitude
4.3.3.
Relative Humidity
Relative Humidity Limit
4.3.4.
Vibration Levels
Bump Test
Random Vibration Test
Sinusoidal vibration test

4.4. Response Times

Command Source
Response Time
STO Input
<25ms
Digital Input
<8ms
Analog Input
<16ms
Modbus RTU Interface
<8ms From receipt of valid command
BACnet MSTP Interface
<8ms From receipt of valid command
Extended I/O Option
<8ms
Plug In Fieldbus Option
<20ms + Fieldbus Cycle Time From receipt of valid command
Master / Slave Function
<8ms, response, 60ms cycle
Power Stage
<10ms to enable output
IP20 Drives : -10 - +50°C (14 - 122°F) without derating
IP55 & IP66 Drives : -10 - + 40°C (14 - 104°F) without derating
-40 ... 60 ºC. No Frost or Condensation
1000m Derate above 1000m by 1% per 100m
2000m
4000m
95% Maximum, non-condensing
Testing in each of three mutually perpendicular axes in turn.
Reference standard: IEC 60068-2-29
Severity: 18g, 6ms, half sine
No of bumps: 600 (100 per axis)
BS EN61800-5-1
BS EN61800-5-1