Changing Parameters And Settings Using A 'Bop' / 'Aop - Siemens MICROMASTER 420 Getting Started Manual

Hide thumbs Also See for MICROMASTER 420:
Table of Contents

Advertisement

4.5

Changing parameters and settings using a 'BOP' / 'AOP'

The following description shows how to change the parameter P1082. Use this
description as a guide for setting any parameters using the 'BOP'.
Step
1
Press
to access parameters
Press
until P0010 is
2
displayed
Press
to access P0010
3
Value level
Press
to set P0010 = 1
4
Press
to save and exit
5
value level
Press
until P1082 is
6
displayed
Press
to access P1082
7
value level
Press
to select desired
8
maximum frequency.
Press
to save and exit
9
value level
10
Press
to return to P0010
Press
to access P0010
11
value level
Press
to return value to
12
P0010 = 0
Press
to save and exit
13
value level
14
Press
to return to r0000
Press
to exit
15
Parameterization
The LCD will alternate between
actual frequency and the
requested frequency setpoint
The required maximum frequency has now been stored.
Getting Started Guide – September 2000
6SE6400-5AB00-0BP0
Result on display
H
P(1)
2
P(1)

P(1)

P(1)
2
P(1)
2&
P(1)
P(1)
50.00
P(1)
35.00
2&
P(1)
2
P(1)

P(1)

P(1)
2
P(1)
H
P(1)
P(1)
35.00

P(1)
.00
9