4.2

Commissioning with Getting Started Guide

Mechanical Installation
Page 3
Electrical Installation
Page 4
Commissioning with
Commissioning with
SDP
BOP
Page 7
Page 8
Command Source:
Default (P0700 = 2)
Connecting an On/Off Switch
Connecting a Potentiometer for Speed setting
Connecting a Switch for reversing
Starting the motor using an
external ON / OFF switch
4.3

Commissioning with the Status Display Panel

When commissioning the MICROMASTER 420 with the Status Display Panel
(SDP), the drive application must be covered by the default settings of your
MICROMASTER 420.
Connect On/Off Switch to the terminals 5 and 8
Connect Switch for reversing direction to the terminals 6 and 8 (Optional)
Connect Switch for fault reset to the terminals 7 and 8 (Optional)
Connect analog frequency display to the terminals 12 and 13 (Optional)
Connect Output relay to the terminals 10 and 11 (Optional)
Connect a 5.0 kΩ Potentiometer for speed control to the terminals 1 to 4
The Inverter is now ready for starting.
Getting Started Guide – September 2000
6SE6400-5AB00-0BP0
Command Source:
BOP (P0700 = 1)
Starting the motor via
The 'BOP'